1.12.3 ARH/ARD 075 Cooling capacities
Return air Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC 35 ºC 46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil Input temp. TS in indoor coil Input temp. TS in indoor coil
30 27 24 22 30 27 24 22 30 27 24 22
(Mini‐
mum)
11500
23 81.1 19.6 49.2 38.6 28 - 76.9 21.4 47.8 37.2 26.6 - 69.3 23.7 45.4 34.8 24.1 -
19 73.5 19 65.2 54.6 43.9 36.8 69.3 20.6 63.5 52.9 42.3 35.2 62.4 22.2 61 50.3 39.7 32.6
17 69.3 18.5 69.3 62.2 51.7 52 63.8 20.4 63.8 59.7 49.1 46 56.8 22 56.8 56.8 46.3 39.3
15 62.4 18.3 62.4 62.4 57.6 50.5 59.6 20 59.6 59.6 53.1 49.1 53.3 21.8 53.3 53.3 53.3 46.5
(Nomi‐
nal)
13500
23 83.5 19.9 53.3 41.1 28.9 - 79.3 21.7 51.9 39.6 27.4 - 71.4 24 49.5 37.2 25 -
19 75.7 19.2 71.6 59.3 47.1 38.9 71.4* 20.9* 69.9 57.6* 45.4 37.2 64.3 22.6 64.3 55.1 42.8 34.7
17 71.4 18.8 71.4 68.2 55.9 58 65.7 20.7 65.7 65.5 53.3 50.3 58.5 22.4 58.5 58.5 50.6 42.4
15 64.2 18.6 64.2 64.2 63 54.8 61.4 20.3 61.4 61.4 61.4 53.3 55 22.2 55 55 55 50.7
(Maxi‐
mum)
16000
23 85.9 20.1 58.3 44 29.8 - 81.5 22 56.8 42.6 28.3 - 73.4 24.4 54.4 40.2 25.9 -
19 77.8 19.5 77.8 65 50.7 41.3 73.4 21.2 73.4 63.3 49 39.6 66.1 22.9 66.1 60.7 46.5 37
17 73.4 19.1 73.4 73.4 61 60.6 67.5 21 67.5 67.5 58.4 55.5 60.2 22.7 60.2 60.2 55.6 46.1
15 66.1 18.9 66.1 66.1 66.1 60 63.1 20.6 63.1 63.1 63.1 58.4 56.5 22.5 56.5 56.5 56.5 55.8
* Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.12.4 ARH/ARD 090 Cooling capacities
Return air Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC 35 ºC 46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil Input temp. TS in indoor coil Input temp. TS in indoor coil
30 27 24 22 30 27 24 22 30 27 24 22
(Mini‐
mum)
13000
23 93.8 22.9 57.6 45 32.4 - 89 25.1 55.9 43.3 30.7 - 80.2 27.7 53.2 40.5 28 -
19 85 22.2 76.5 63.9 51.3 42.9 80.2 24.1 74.5 61.9 49.4 41 72.2 26 71.6 59 46.4 38
17 80.2 21.7 80.2 73 60.4 56 73.8 23.9 73.8 70 57.4 51.1 65.8 25.8 65.8 65.8 54.3 46
15 72.2 21.4 72.2 72.2 67.5 59.1 69 23.4 69 69 65.8 57.4 61.7 25.5 61.7 61.7 61.7 54.5
(Nomi‐
nal)
16000
23 97.6 23.4 64.4 49.1 33.8 - 92.6 25.6 62.7 47.4 32.1 - 83.4 28.3 60 44.6 29.3 -
19 88.4 22.6 87 71.7 56.4 46.2 83.4* 24.6* 83.4 69.7* 54.5 44.2 75.1 26.6 75.1 66.8 51.5 41.3
17 83.4 22.1 83.4 82.7 67.4 63.6 76.7 24.4 76.7 76.7 64.4 57.3 68.4 26.3 68.4 68.4 61.2 51
15 75.1 21.9 75.1 75.1 75.1 66.2 71.7 23.9 71.7 71.7 71.7 64.5 64.2 26.1 64.2 64.2 64.2 61.5
(Maxi‐
mum)
18000
23 99.5 23.7 68.7 51.6 34.5 - 94.3 25.9 67 50 32.9 - 85 28.6 64.2 47.2 30.1 -
19 90.1 22.9 90.1 76.7 59.6 48.2 85 24.9 85 74.8 57.7 46.3 76.5 26.9 76.5 71.8 54.7 43.3
17 85 22.4 85 85 71.9 68.6 78.2 24.7 78.2 78.2 68.9 61.2 69.7 26.6 69.7 69.7 65.7 54.3
15 76.5 22.2 76.5 76.5 76.5 70.7 73.1 24.2 73.1 73.1 73.1 68.8 65.5 26.4 65.5 65.5 65.5 65.5
* Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.12.5 ARH/ARD 045 Thermodynamic heat capacity
Flow
m
3
/h
Return
air TS
ºC
Outdoor air temperature TS ºC
-10 -5 0 5 7 10 15 20
PT PC PT PC PT PC PT PC PT PC PT PC PT PC PT PC
(Minimum)
7000
14 30.2 10.2 34.1 10.7 38.6 11.1 43.5 11.4 45.6 11.9 48.9 12.3 54.8 13.2 61.1 13.7
17 29.8 11.1 33.7 11.6 38.1 12.1 43 12.3 45.1 12.9 48.3 13.4 54.2 14.3 60.4 14,9
20 29.5 11.4 33.3 11.8 37.7 12.3 42.5 12.6 44.6 13.2 47.8 13.7 53.6 14.7 59.7 15.2
23 29.1 12.1 32.9 12.6 37.2 13.2 42 13.5 44 14.1 47.2 14.6 52.9 15.7 59 16.2
25 28.9 12.5 32.7 13 37 13.6 41.7 13.9 43.7 14.5 46.9 15 52.6 16.1 58.6 16.7
(Nominal)
8500
14 30.6 9.9 34.6 10.3 39.2 10.8 44.2 11 46.3 11.6 49.6 12 55.6 12.8 62 13.3
17 30.2 10.8 34.2 11.2 38.7 11.7 43.6 12 45.7 12.5 49 13 55 13.9 61.3 14.4
1 Installation manual
1.12 ARH/ARD Output
16