ARI RATINGS
1
- COOLING, HEATING AND SOUND
SYSTEM APPLICATION DATA
The coils for both the indoor and outdoor units are not only
circuited and headered for optimum heating and cooling
performance, but also for ample subcooling during all modes
of operation. The sub-cooling permits the outdoor unit to be
mounted 60 feet over or under the indoor unit without any
danger of flashing liquid refrigerant during the heating or the
cooling cycle.
Refer to the REFRIGERANT PIPING table above for more
detailed information on refrigerant pipe limitations.
A = 1-3/8" OD Vapor Line
B = 1-1/8" OD Vapor Line
C = Intermediate Trap - only required when a riser exceeds
50 feet.
D = Inverted Trap - only required when the horizontal run to
the unit exceeds 25 feet.
Model Cooling Capacity
Heating Capacity
High Outdoor
Temperature (47
°
F)
Low Outdoor
Temperature (17
°
F)
Outdoor
Unit
Indoor
Unit
MBH
3
EER MBH
3
COP MBH
3
COP
E2FB090 F3EH090 91 9.2 86 3.0 55 2.08
E1FB120 F3EH120 121 9.0 117 3.0 63 2.1
Outdoor Unit
Sound Rating
2
(bels)
E2FB090 8.6
E1FB120 9.0
1Ratings are in accordance with ARI Standard 240.
2Sound ratings are in accordance with ARI Standard 270.
3Deduct 1 MBH when a unit operates at 208 volts.
Air Temperature on OUTDOOR Coil,
°
F Air Temperature on INDOOR Coil,
°
F
Minimum Maximum Minimum Maximum
Cool Heat Cool Heat Cool Heat Cool Heat
40 db 0 db
1
115 db 75 db 57 wb 50 db
2
72 wb 80 db
Air Flow across INDOOR Coil, CFM (Min./Max.)
FEH090 2400/3600
FEH120 3200/4800
1Below 0
°
F, the control circuit will lock out the compressor and allow the electric heat
accessory to cycle at its standby capacity.
2Operation below this temperature is permissible for a short period of time when a unit is
required to heat the conditioned space up to 50
°
F.
System
(Tons)
Maximum
Vertical Rise,
2
(Feet)
Maximum
Total Length,
(Feet)
7-1/2 60 125
10 60 100
1Refer to installation instruction Form 515-41-N1Y for more detailed information on
refrigerant piping.
2Based on the loss of static head in the liquid riser during the heating cycle.
REFRIGERANT PIPING LIMITATIONS
1
SYSTEM FLEXIBILITY
515.41-TG1Y
Unitary Products Group 3