BLOWER MOTOR AND DRIVE DATA
RPM
CFM
ESP
2
BHP KW ESP
2
BHP KW ESP
2
BHP KW ESP
2
BHP KW ESP
2
BHP KW
F3EH090
2400 2700 3000 3300 3600
600 0.30 0.62 0.79 0.21 0.70 0.76 0.09 0.78 0.89 - - - - - -
655 0.43 0.70 0.86 0.39 0.78 0.83 0.26 0.87 0.97 0.11 0.96 1.07 - - -
700 0.52 0.77 0.93 0.48 0.85 0.90 0.40 0.95 1.06 0.28 1.06 1.16 0.14 1.17 1.26
800 0.82 0.97 1.10 0.81 1.06 1.07 0.74 1.18 1.27 0.63 1.30 1.38 0.51 1.42 1.49
880 1.10 1.11 1.24 1.09 1.24 1.21 1.02 1.37 1.45 0.91 1.50 1.55 0.78 1.64 1.70
900 1.15 1.15 1.27 1.14 1.28 1.24 1.07 1.42 1.49 0.97 1.55 1.60 0.87 1.70 1.74
1000 1.49 1.35 1.46 1.47 1.48 1.43 1.42 1.63 1.65 1.35 1.81 1.82 1.27 2.02 2.02
F3EH120
3200 3600 4000 4400 4800
700 0.39 1.01 1.17 0.26 1.17 1.27 0.05 1.33 1.38 - - - - - -
800 0.75 1.25 1.38 0.63 1.42 1.51 0.43 1.60 1.64 0.22 1.80 1.78 - - -
900 1.08 1.48 1.60 0.98 1.70 1.77 0.81 1.92 1.93 0.61 2.18 2.09 0.34 2.45 2.23
950 1.29 1.61 1.71 1.19 1.86 1.90 1.02 2.12 2.07 0.86 2.39 2.23 0.56 2.67 2.42
1000 1.46 1.75 1.83 1.38 2.02 2.02 1.23 2.30 2.20 1.06 2.60 2.39 0.78 2.90 2.59
1Unit resistance is based on a wet indoor coil and clean filters.
2
Available static pressure in IWG to overcome the resistance of the duct system and any accessoires added to the unit. Refer to the table above for additional motor and drive data and to the
table on page 7 for the resistance of these accessories.
3
Refer to Form 515.41-AD1 for blower performance curves.
SUPPLY AIR BLOWER PERFORMANCE
1,3
Indoor
Unit
Model
Motor*
HP
Blower
HP
Adjustable Motor Pulley Fixed Blower Pulley Belt
Pitch Diameter,
(in.)
Bore,
(in.)
Pitch Diameter,
(in.)
Bore,
(in.)
Designation
Pitch Length,
(in.)
FEH090 1-1/2 655-880
2.8 - 3.8 7/8
7.5
1 A36 37.3
FEH120 2 700-950 7.0
**These motors will always be wired for a 460 volt power supply. Refer to the wiring
diagram inside the motor terminal box when the motor leads have to be reconnected
for a 208 or 230 volt power supply.
*Motor Specifications:
1750 RPM
inherently protected
208/230/460-3-60**
or 380/415-3-50
1.15 service factor
solid base
permanently lubricated
56 frame
llllball bearings
RPM range for the standard drive components.
Exceeds the BHP limitations of the standard blower motor.
SUPPLY AIR PLENUM PERFORMANCE
18˚
22-1/2˚
45˚
18˚
18˚
Indoor
Unit
Model
FEH
CFM
Face
Velo-
city
(FPM)
Angle of Deflection
Vertical
Louvers
1
(Plan View)
Horizontal
Louvers
2
(Elevation
View)
Vertical
Louvers
1
(Plan View)
Horizontal
Louvers
2
(Elevation
View)
Vertical
Louvers
1
(Plan View)
Horizontal
Louvers
2
(Elevation
View)
Throw
(Feet)
3
Spread
(Feet)
3
Throw
(Feet)
3
Spread
(Feet)
3
Throw
(Feet)
3
Spread
(Feet)
3
Min. Max. Min. Max. Drop (Feet)
4
Min. Max. Min. Max. Drop (Feet)
4
Min. Max. Min. Max. Drop (Feet)
4
090
2400 615 47 74 20 29 19 9 34 53 23 33 17 8 26 39 45 65 9 5
2700 690 53 83 22 32 20 10 39 59 25 36 18 9 29 45 48 71 10 5
3000 770 59 92 24 35 21 10 42 66 27 40 19 9 32 50 52 78 10 5
3300 845 65 101 26 38 21 10 46 73 29 44 19 9 35 55 56 85 10 5
3600 920 71 110 28 41 22 11 50 79 32 47 20 10 38 60 60 91 11 6
120
3200 820 63 98 25 37 21 10 45 70 29 43 19 9 34 53 54 82 10 5
3600 920 71 110 28 41 22 11 50 79 32 47 20 10 38 60 60 91 11 6
4000 1025 78 123 30 45 22 11 56 88 35 52 20 10 42 66 67 102 11 6
4400 1130 86 135 33 49 23 12 62 97 38 57 21 11 47 73 76 115 12 6
4800 1230 94 147 35 53 23 12 68 106 41 62 21 11 51 80 85 127 12 6
1Adjusting the vertical louvers will vary the throw, the spread and the drop.
2
Adjusting the horizontal louvers will only vary the drop.
3
The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.
4
The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occupied level of the conditioned space.