EasyManua.ls Logo

York E2FB090 - UNIT DIMENSIONS & CLEARANCES - OUTDOOR UNITS; Outdoor Unit Clearances; Outdoor Unit Center of Gravity

York E2FB090
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.
CLEARANCES
Overhead (Top)
1
120"
Front
(Piping and Access Panels)
30"
Left Side 24"
Right Side 24"
Rear 24"
Bottom
2
0"
1Units must be installed oudoors. Overhanging structures or shrubs should
not obstruct air discharge outlet.
2
Adequate snow clearance must be provided if winter operation is expected.
UNIT DIMENSIONS & CLEARANCES -
OUTDOOR UNITS
FRONT
APPROXIMATE
CENTER OF GRAVITY
BACK
(COIL END)
A
C
D
B
AIR
OUT
AIR
IN
4-5/8
25-3/4
10-1/8
2-1/2
4-1/2
GUAGE
LINE
ACCESS
1- 3/8" OD
SUCTION CONN.
5/8" OD
LIQUID CONN.
COMPRESSOR AND
CONDENSER FAN MOTOR
ACCESS
7/8: KNOCKOUT
ACCESSORY WIRING
ENTRY
1-3/8" DIA.
POWER WIRING
ENTRY
7/8" DIA.
CONTROL WIRING
ENTRY
32-1/2
5
4-1/8
2
5
CONTROL BOX
ACCESS
31-3/4
42-3/4
* AIR ON 3 SIDES
EFB090
(7-1/2 Ton)
AIR
OUT
AIR
IN
AIR
OUT
2-3/4
32
2-1/4
32-1/2
70-1/8
8-3/4
5-3/8
CONTROL BOX
ACCESS
GUAGE
LINE
ACCESS
39
1-3/8* OD
VAPOR LINE
5/8* OD
LIQUID LINE
14-3/4
7/8 DIA
CONTROL WIRING
ENTRY
COMPRESSOR AND
CONDENSER FAN MOTOR
ACCESS
1-3/8 DIA.
POWER WIRING
ENTRY
6-3/4
CONDENSER FAN MOTOR
ACCES
7/8" KNOCKOUT
ACCESSORY WIRING
ENTRY
6-3/4
5-7/8
*AIR ON 3 SIDES
EFB120
(10 Ton)
CENTER OF GRAVITY
Unit
Dim. (inches.)
ABCD
7-1/2 Ton 42-3/4 31-3/4 21-1/4 11-1/2
10 Ton 70-1/8 32 29-5/8 16-1/2
515.41-TG1Y