SM-18001-rev.1
5-27
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(35) Not Prepared (d6)
(36) Not Prepared (d7)
(37) Not Prepared (E1)
(38) Not Prepared (E2)
(39) Not Prepared (E3)
(40) Not Prepared (E4)
(41) Not Prepared (E5)
(42) Indoor Fan Operation Time After Cooling Operation Stoppage (E6)
Thisfunctionisutilizedtopreventcondensationuponcoolingoperationstoppagebysetting“SLOW”
indoorfanoperationtodry.“SLOW”operation(for60minutesor120minutesbysetting)continues
evenwhenthecoolingoperationisstopped.
(43) Not Prepared (E7)
(44) Fan Operation Control during Heating Thermo-OFF (E8)
Thisfunctionisutilizedtopreventtheperceptionofcolddraftbyreducingtheindoorfanspeedduring
heatingThermo-OFF.
(32) Power Supply ON/OFF 2 (Restarting Function After Power Failure) (d3)
Thisfunctionisutilizedtorestarttheunitoperationautomaticallywhenthepowersupplyisrestored
afterapowerfailureofover2seconds.Incaseofpowerfailurefor2secondsorless,thestandard
unitretainsalltheoperationalfunctionsandrestartstheoperationautomatically.(Thecompressor
restartsoperationafter3minutesguardinadditiontopowerfailuretimeforupto2seconds.)
Whenthisfunctionisutilizedintheconditionthatthereisnopersontooperatetheunit,monitorthe
systemforpotentialunitfailure.
NOTES:
1. Ifpowerfailureoccursduringthestoppageoftheunit,theunitremainsstoppedafterthepower
supplyisrestored.
2. Whenthecompressordoesnotreachthexedtemperature,thesystemmaynotrestart
automaticallyafterturningonthepowersupplybyhot-startcontrol.
*Hot-startControl: Thecontrolprogramthatdoesnotoperatethecompressorevenafterthe
poweristurnedONifthecompressordoesnotreachthexedtemperature.
(33) Prevention for Cooling Discharge Air Temperature Decrease (d4)
Thisfunctionisutilizedtopreventdischargeairtemperaturedecreaseduringthecoolingoperationby
controllingThermo-ON/OFFaccordingtothedischargeairtemperature.
●Thermo-ON:
COOL/DRYoperationscontinuefor3minuteswhendischargeairtemperatureat52
o
F(11
o
C)orlower.
●Thermo-OFF:
Theroomtemperaturereachesthesettingtemperaturewhendischargeairtemperatureat56
o
F(13
o
C)
orhigher.
(34) Not Prepared (d5)...(forDuctedHighStaticType)
(34) Prevention for Heating Discharge Air Temperature Decrease (d5)...(forDuctedMediumStaticand
SlimType)
Thisfunctionisutilizedtopreventdischargeairtemperaturedecreaseduringtheheatingoperationby
makingtheactualfanspeedlowerthanthespeedindicatedonthewiredcontroller.
NOTE:
Theabovetableshowswhentheoptionalfunctionsetting“HiSpeed”issetasstandard(00)bythe
wiredcontroller.
Large Fan Speed Small
Indications on
WiredController
HIGH2 HIGH MED LOW
Actual Fan Speed HIGH HIGH LOW LOW
SettingCondition Fan Operation
during
Thermo-OFF
00 LOW
01 SLOW