(42) Indoor Fan Operation Time After Cooling Operation Stoppage (E6)
Thisfunctionisutilizedtopreventcondensationuponcoolingoperationstoppagebysetting“SLOW”
indoorfanoperationtodry.“SLOW”operation(for60minutesor120minutesbysetting)continues
evenwhenthecoolingoperationisstopped.
(43) Not Prepared (E7)
(44) Fan Operation Control during Heating Thermo-OFF (E8)
Thisfunctionisutilizedtopreventtheperceptionofcolddraftbyreducingtheindoorfanspeedduring
heatingThermo-OFF.
(32) Power Supply ON/OFF 2 (Restarting Function After Power Failure) (d3)
Thisfunctionisutilizedtorestarttheunitoperationautomaticallywhenthepowersupplyisrestored
afterapowerfailureofover2seconds.Incaseofpowerfailurefor2secondsorless,thestandard
unitretainsalltheoperationalfunctionsandrestartstheoperationautomatically.(Thecompressor
restartsoperationafter3minutesguardinadditiontopowerfailuretimeforupto2seconds.)
Whenthisfunctionisutilizedintheconditionthatthereisnopersontooperatetheunit,monitorthe
systemforpotentialunitfailure.
NOTES:
1. Ifpowerfailureoccursduringthestoppageoftheunit,theunitremainsstoppedafterthepower
supplyisrestored.
2. Whenthecompressordoesnotreachthexedtemperature,thesystemmaynotrestart
automaticallyafterturningonthepowersupplybyhot-startcontrol.
*Hot-startControl: Thecontrolprogramthatdoesnotoperatethecompressorevenafterthe
poweristurnedONifthecompressordoesnotreachthexedtemperature.
(33) Prevention for Cooling Discharge Air Temperature Decrease (d4)
Thisfunctionisutilizedtopreventdischargeairtemperaturedecreaseduringthecoolingoperationby
controllingThermo-ON/OFFaccordingtothedischargeairtemperature.
●Thermo-ON:
COOL/DRYoperationscontinuefor3minuteswhendischargeairtemperatureat52
o
F(11
o
C)orlower.
●Thermo-OFF:
Theroomtemperaturereachesthesettingtemperaturewhendischargeairtemperatureat56
o
F(13
o
C)
orhigher.
(34) Not Prepared (d5)...(forDuctedHighStaticType)
(34) Prevention for Heating Discharge Air Temperature Decrease (d5)...(forDuctedMediumStaticand
SlimType)
Thisfunctionisutilizedtopreventdischargeairtemperaturedecreaseduringtheheatingoperationby
makingtheactualfanspeedlowerthanthespeedindicatedonthewiredcontroller.
NOTE:
Theabovetableshowswhentheoptionalfunctionsetting“HiSpeed”issetasstandard(00)bythe
wiredcontroller.
Large Fan Speed Small
Indications on
WiredController
HIGH2 HIGH MED LOW
Actual Fan Speed HIGH HIGH LOW LOW
SettingCondition Fan Operation
during
Thermo-OFF
00 LOW
01 SLOW