102777-YIM-E-0206
Unitary Products Group 29
TABLE 21: ELECTRICAL DATA BASIC UNIT WITH POWER EXHAUST - 40 TON
VOLTAGE
SUPPLY AIR MOTOR EXHAUST OR ERV FAN MOTOR(S) BASIC UNIT WITH EXHAUST FAN
HP HP FLA MCA
MAX. OVERCURRENT
PROTECTION DEVICE (MOPD)
208-3-60
10
7.5 24.2 235 250
10 (5 x 2) 30.8 241 250
15 (7.5 x 2) 46.2 259 300
15
7.5 24.2 252 300
10 (5 x 2) 30.8 259 300
15 (7.5 x 2) 46.2 274 300
20
7.5 24.2 268 300
10 (5 x 2) 30.8 275 300
15 (7.5 x 2) 46.2 290 300
25
7.5 24.2 288 350
10 (5 x 2) 30.8 294 350
15 (7.5 x 2) 46.2 310 350
230-3-60
10
7.5 22 228 250
10 (5 x 2) 28 234 250
15 (7.5 x 2) 42 249 250
15
7.5 22 243 250
10 (5 x 2) 28 249 250
15 (7.5 x 2) 42 263 300
20
7.5 22 258 300
10 (5 x 2) 28 264 300
15 (7.5 x 2) 42 278 300
25
7.5 22 275 300
10 (5 x 2) 28 281 300
15 (7.5 x 2) 42 295 350
460-3-60
10
7.5 11 112 125
10 (5 x 2) 14 115 125
15 (7.5 x 2) 21 123 125
15
7.5 11 120 125
10 (5 x 2) 14 123 125
15 (7.5 x 2) 21 130 150
20
7.5 11 127 150
10 (5 x 2) 14 130 150
15 (7.5 x 2) 21 137 150
25
7.5 11 136 150
10 (5 x 2) 14 139 150
15 (7.5 x 2) 21 146 175
575-3-60
10
7.5 9 92 100
10 (5 x 2) 11 94 110
15 (7.5 x 2) 17 101 110
15
7.5 9 99 110
10 (5 x 2) 11 101 110
15 (7.5 x 2) 17 107 110
20
7.5 9 105 125
10 (5 x 2) 11 107 125
15 (7.5 x 2) 17 113 125
25
7.5 9 111 125
10 (5 x 2) 11 113 125
15 (7.5 x 2) 17 119 125