102777-YIM-E-0206
38 Unitary Products Group
575-3-60
40 40
10
7.5 9 92 100
10 (5 x 2) 11 94 110
15(7.5 x 2) 17 101 110
15
7.5 9 99 110
10 (5 x 2) 11 101 110
15(7.5 x 2) 17 107 110
20
7.5 9 105 125
10 (5 x 2) 11 107 125
15(7.5 x 2) 17 113 125
25
7.5 9 111 125
10 (5 x 2) 11 113 125
15(7.5 x 2) 17 119 125
80 80
10
7.5 9 105 110
10 (5 x 2) 11 108 110
15(7.5 x 2) 17 115 125
15
7.5 9 113 125
10 (5 x 2) 11 115 125
15(7.5 x 2) 17 123 125
20
7.5 9 119 125
10 (5 x 2) 11 122 125
15(7.5 x 2) 17 129 150
25
7.5 9 125 150
10 (5 x 2) 11 128 150
15(7.5 x 2) 17 135 150
108 108
10
7.5 9 133 150
10 (5 x 2) 11 136 150
15(7.5 x 2) 17 143 150
15
7.5 9 141 150
10 (5 x 2) 11 143 150
15(7.5 x 2) 17 151 175
20
7.5 9 147 150
10 (5 x 2) 11 150 150
15(7.5 x 2) 17 157 175
25
7.5 9 153 175
10 (5 x 2) 11 156 175
15(7.5 x 2) 17 163 175
TABLE 24: ELECTRICAL DATA BASIC UNIT W/ POWER EXHAUST & ELECTRIC HEAT - 40 TON (Continued)
VOLTAGE
ELECTRIC HEAT
SUPPLY AIR
MOTOR
EXHAUST OR ERV FAN
MOTOR(S)
BASIC UNIT WITH EXHAUST FAN
AND ELECTRIC HEAT
NOMINAL
KW
APPLIED KW HP HP FLA MCA
MAX. OVERCURRENT
PROTECTION