Table 29: YV28 to YV50 VFD four-stage standard static with modulating power exhaust
Comp. 1 Comp. 2 Comp. 3
Min
disconnect
rating
Min
disconnect
rating/120V
trans
Size
(tons)
Nominal
unit
voltage
RLA LRA RLA LRA RLA LRA
OD fan
motors
each
FLA
OD fan
motors
each
FLA
Supply
blower
motor
FLA
Supply
blower
motor
LRA
Power
exhaus
t VFD
FLA
Power
exhaus
t motor
LRA
120 V
trans
FLA
MCA
A
Max
f/b
size
A
FLA LRA
MCA
with
120 V
trans
A
Max
f/b
size
with
120V
trans
A
FLA LRA
208-3-60 41.0 304 22.4 149 22.4 149 4.0 21.0 22.0 144.4 9.6 21.0 14.4 144 175 153 872 158 175 170 887
230-3-60 41.0 304 22.4 149 22.4 149 4.2 21.0 22.0 144.4 9.6 21.0 13.0 144 175 154 872 157 175 169 885
460-3-60 19.2 147 10.6 75 10.6 75 2.1 10.5 11.0 72.2 4.8 10.5 6.5 69 80 74 432 76 90 82 439
YV28
(27.5)
575-3-60 16.7 122 7.7 54 7.7 54 1.6 7.8 9.0 59.1 4.9 7.8 5.2 57 70 60 336 62 75 66 341
208-3-60 44.2 315 25 164 25 164 4.0 21.0 22.0 144.4 9.6 21.0 14.4 153 175 163 913 167 200 180 928
230-3-60 44.2 315 25 164 25 164 4.2 21.0 22.0 144.4 9.6 21.0 13.0 154 175 164 913 167 200 179 926
460-3-60 22.4 158 12.8 100 12.8 100 2.1 10.5 11.0 72.2 4.8 10.5 6.5 78 100 83 493 84 100 91 500
YV30
(30)
575-3-60 18.6 136 9.6 78 9.6 78 1.6 7.8 9.0 59.1 4.9 7.8 5.2 63 80 67 398 68 80 73 403
208-3-60 48.1 351 27.6 191 27.6 191 4.0 21.0 22.0 144.4 9.6 21.0 14.4 163 200 174 1003 177 225 190 1018
230-3-60 48.1 351 27.6 191 27.6 191 4.2 21.0 22.0 144.4 9.6 21.0 13.0 164 200 174 1003 177 200 189 1016
460-3-60 24.7 197 12.8 100 12.8 100 2.1 10.5 11.0 72.2 4.8 10.5 6.5 81 100 86 532 87 110 93 539
YV35
(35)
575-3-60 22.4 135 9.6 78 9.6 78 1.6 7.8 9.0 59.1 4.9 7.8 5.2 68 80 71 397 73 90 77 402
208-3-60 48.1 351 27.6 191 27.6 191 4.0 21.0 28.0 173.44 15.2 39.6 14.4 175 200 187 1070 189 225 203 1084
230-3-60 48.1 351 27.6 191 27.6 191 4.2 21.0 28.0 173.44 15.2 39.6 13.0 175 200 188 1070 188 225 203 1083
460-3-60 24.7 197 12.8 100 12.8 100 2.1 10.5 14.0 86.72 8.2 19.8 6.5 87 110 93 565 94 110 101 572
YV40
(40)
575-3-60 22.4 135 9.6 78 9.6 78 1.6 7.8 11.0 71.77 6.1 15.8 5.2 71 90 75 426 76 90 81 431
208-3-60 67.3 485 39.1 267 39.1 267 7.2 39.6 28.0 173.44 15.2 39.6 14.4 234 300 250 1430 249 300 267 1444
230-3-60 67.3 485 39.1 267 39.1 267 6.8 39.6 28.0 173.44 15.2 39.6 13.0 233 300 248 1430 246 300 263 1443
460-3-60 32.7 215 18.6 142 18.6 142 3.4 19.8 14.0 86.72 8.2 19.8 6.5 114 125 122 705 120 150 129 711
YV50
(50)
575-3-60 26.3 175 15.4 103 15.4 103 2.7 15.8 11.0 71.77 6.1 15.8 5.2 92 110 98 548 97 110 104 553
Installation Manual: YORK
®
Sun
Select YV28 to YV50
51
Johnson Controls Ducted Systems