SECTION 6 – OPERATION
To view the Minutely Operation History screen, press
the Minutely Operation button in the History Menu
section of the Data screen.
The Minutely Operation History screen shows opera-
tional information for the last 12 minutes and contains
the following fields of information:
Operation: operation status of the chiller
Ope. Method: selected operation method
Sol. Pump: operation status of the solution pump
Ref. Pump: operation status of the refrigerant pump
Ope. Hours: how many hours the chiller has been run-
ning
Ope. Freq.: how many times the chiller has started us-
ing the OPER. button or the remote start signal
Fail. Freq.: how many times the chiller has had a fail-
ure alarm
Alarm Freq.: how many times an alarm has been trig-
gered for the chiller
Purge Freq.: how many times a purge has been per-
formed automatically
The Chilled water section of the screen shows you the
following information:
In Temp.: temperature of the chilled water measured
as it enters the evaporator.
Out Temp.: temperature of the chilled water measured
as it leaves the evaporator.
The Cooling Water section shows you:
In Temp.: temperature of the cooling water measured
as it enters the absorber.
Out Temp.: temperature of the cooling water mea-
sured as it leaves the condenser.
Ref. Temp.: temperature of the refrigerant in the evap-
orator.
Abs. Temp.: temperature of the diluted solution in the
absorber.
MINUTELY OPERATION HISTORY SCREEN
LD20033_UL
FIGURE 53 - MINUTELY OPERATION HISTORY SCREEN