JOHNSON CONTROLS
162
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
SECTION 8 – TROUBLESHOOTING
INSUFFICIENT VACUUM LEVELS
Causes of insufficient vacuum level of purging line and
countermeasures against them.
TABLE 47 - INSUFFICIENT VACUUM LEVELS
ITEM CAUSE COUNTERMEASURE
1 Purge pump trouble Contact your local Johnson Controls Service Ofce.
2 Deterioration of vacuum pump oil Replace the vacuum pump oil.
3
Wrong operation of purging line switching when
vacuum pump capacity was checked
See Purge Procedure on page 130. Conrm the valves
are open or closed.
4 Deterioration of vacuum pump belt
Contact your local Johnson Controls Service Ofce.
5 Leakage in purge pipe line
6 Blocked or dysfunctional purge solenoids
7 Check valve does not open
8 Valve V21 mistakenly open
See Purge Procedure on page 130. Conrm the valves
are open or closed.
ACTIONS TO TAKE AGAINST POWER
FAILURE
If the main power fails, follow the steps in the flow-
chart shown Figure 67 on page 163 and Figure 68 on
page 164.