JOHNSON CONTROLS
39
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
4
SECTION 4 - TECHNICAL DATA
This section includes technical information
about the unit, such as weight, dimensions, and
electrical data.
The numbers shown in Table 7 on page 39 are the
allowable ranges for each parameter. Not all combi-
nations are possible. Please check with your Johnson
Controls Service Center to see if your temperature dif-
ferential is possible.
TABLE 7 - TYPICAL OPERATIONAL RANGE
PARAMETER
ALLOWABLE RANGES
EUROPE FOR OTHER
COUNTRIES
OPTIONAL
Chilled Water In 44.6 - 77 °F 39.2 - 44.6 °F
Chilled Water Out 39.2 - 60.8 °F 33.8 - 39.2 °F
Cooling Water In 68 - 98.6 °F
Cooling Water Out 77 - 107.6 °F
CL
Hot Water In 158 - 230 °F 158 - 210.2 °F
Hot Water Out 140 - 228.2 °F 140 - 208.4 °F
CH
Hot Water In 231.8 - 320 °F 212 - 320 °F
Hot Water Out 176 - 302 °F 176 - 302 °F