York YHAU-CL Series - TABLE 27 - Safety Switches

York YHAU-CL Series
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
127
SECTION 6 – OPERATION
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
6
TABLE 27 - SAFETY SWITCHES
SAFETY SWITCH NAME LOCATION SYMBOL OPERATION
Chilled water differential pressure switch 69WC1 Operates when the ow rate lowers.
Solution circulating pump thermal switch
In control
panel
Th1
Operates when the current rises above the
set value.
Solution spray pump thermal switch Th2
Refrigerant pump thermal switch Th3
Chilled water overcooling switch
Soft switch of
sequencer
26WL
Operates when the chilled water outlet
temperature lowers below the set value.
Refrigerant overcooling switch 26RL
Operates when the refrigerant temperature
lowers below the set value.
Solution high temperature switch 26SH1
Operates when the solution temperature in
the generator rises above the set value.
CONTROL SWITCHES:
ON/OFF operation control switch
Soft switch of
sequencer
23AS
Turns OFF when the chilled water
temperature at the outlet lowers below the
set value and turns ON when the chilled
water temperature rises above the set
value.
Purging tank pressure switch 63AP
Operates when the pressure in purging
tank rises above the set value.
Level switch for evaporator tank
Absorption
chiller unit.
LVS
Operates when the refrigerant level in
evaporator is low.
SENSORS AND GAUGES:
Generator pressure gauge PG1
Purge tank pressure gauge PG2
Purge tank pressure transmitter PT1 Detection of pressure of purge tank.
Pt100 Ω for chilled water inlet temperature TE1 Detection of temperature at each park.
Pt100 Ω for chilled water outlet temperature TE2
Thermocouple for cooling water inlet temperature TE3
Thermocouple for cooling water outlet temperature TE4
Pt100 Ω for refrigerant temperature TE5
Thermocouple for absorber solution temperature TE6
Thermocouple for generator solution temperature TE7
Generator pressure transmitter PT2
Thermocouple for hot water inlet temperature TE8
Thermocouple for hot water outlet temperature TE9

Table of Contents