FORM 160.75-EG1 (519)
JOHNSON CONTROLS
47
TABLE 5 - MOTOR VOLTAGE VARIATIONS
FREQ.
RATED
VOLTAGE
NAMEPLATE
VOLTAGE*
OPERATING VOLTAGE
MIN. MAXIMUM
60 HZ
200 200/208 180 220
230 220/240 208 254
380 380 342 415
416 416 375 457
460 440/460/480 414 508
575 575/600 520 635
2300 2300 2070 2530
3300 3300 2970 3630
4000 4000/4160 3600 4576
50 HZ
346 346 311 381
380 380/400 342 423
415 415 374 440
3300 3300 2970 3630
*For motor voltage above 4160V/60Hz and 3300V/50HZ, contact your JCI Sales Ofce for a specic selection.
MOTOR ELECTRICAL DATA
The smallest motor available which equals or exceeds the Input power (kW) from the
chiller rating program is selected from Table 9 on page 60 to Table 12 on page 62.
The full load amperes (FLA) listed in the tables is maximum values and corresponds to
the maximum motor kW listed. When the input power (kW) is less than maximum motor
kW, the FLA should be reduced per the following equation:
FLA =
Motor kW x Maximum Motor FLA
Maximum Motor kW
The benefit from the FLA correction is the possible use of smaller power wiring and/or
starter size. The locked rotor amperes (LRA) are read directly from Table 9 to Table 12 for
specific Motor Code and voltage.
This is because the LRA is dependent only on motor size and voltage and is independent
of input power (kW). Inrush amperes (IRA) depend on LRA and the type of starter applied.
The inrush can be calculated using a percentage of LRA shown in Table 9 to Table 12.
Application Data (Cont'd)