Application Data (Cont'd)
NOTES:
1. For motor starters above 4160V/60Hz and 3300/50Hz, contact the Johnson Controls Sales Ofce for a specic selection.
2. Minimum tap for 5DJ motor is 80%.
TABLE 13 - MOTOR STARTERS
TYPE
STARTER
SOLID-
STATE
STARTER
STAR
DELTA
AUTO TRANSFORMER
ACROSS-
THE-LINE
PRIMARY REACTOR
VOLTAGE
LOW/
MEDIUM
LOW LOW
LOW/
MEDIUM
LOW/
MEDIUM
LOW/
MEDIUM
MEDIUM MEDIUM
60 HZ 200-4160 200-600 200-600 200-4160 200-4160 200-4160 2300-4160 2300-4160
50 HZ 380-3300 346-415 346-415 346-3300 346-3300 346-3300 2300-3300 2300-3300
TRANSITION
% TAP INRUSH
AS A %
OF LRA
— CLOSED CLOSED CLOSED CLOSED — CLOSED CLOSED
— — 57.7 65 80 — 65 80
45 33 33 42.3 64 100 65 80