Loading...
FORM 160.75-EG1 (519)
JOHNSON CONTROLS
65
Application Data (Cont'd)
TABLE 14 - LOW VOLTAGE VARIABLE SPEED MODELS
MAXIMUM
LRA
MAXIMUM
MOTOR HP
MINIMUM
FLA
MAXIMUM
FLA
RATED
VOLTAGE
ACTUAL
VOLTAGE
PHASE HZ
2500 270 80 364
380 380
3 60
3637 385 120 517
5326 608 200 817
7610 845 300 1126
7527 1100* 300 984
2598 351 80 380
460
440/
460/
480
3652 503 120 565
5777 790 200 880
7014 1048 300 1180
7527 1300* 300 1163
2413 424 80 377
575 575/600
3550 608 120 540
2727 292 80 380
380 380/400
3 50
2895 419 120 565
5780 658 200 880
8205 917 300 1180
7527 1100* 300 984
2366 292 80 362
415 415
3402 419 120 518
5512 704 200 876
6938 900 300 1108
7527 1100* 300 984
NOTE: *1100/1300 HP LVVSD have a 575 Volt / 60 Hz motor. LFA and LRA are for the motor (VSD output).