FORM 160.75-EG1 (519)
JOHNSON CONTROLS
97
SHELLS COMPRESSOR
SHIPPING WEIGHT
LBS. (KGS.)
OPERATING WEIGHT
LBS. (KGS.)
EST. REFRIGERANT
CHARGE LBS. (KGS.)
1
A-A Q3 13100 (5942) 15000 (6804) 828 (376)
C-B Q4 18023 (8175) 22323 (10126) 1525 (692)
C-C Q3, Q4 14920 (6768) 17940 (8138) 1221 (554)
C-C Q5 15330 (6954) 18350 (8324) 1221 (554)
D-D Q3, Q4 17215 (7809) 21100 (9571) 1628 (738)
D-D Q5 17625 (7995) 21510 (9757) 1628 (738)
E-E Q3, Q4 17950 (8142) 22160 (10052) 1710 (776)
E-E Q5,Q6,Q7,P7 18360 (8328) 22570 (10238) 1710 (776)
E-I Q7 23567 (10690) 29384 (13328) 1805 (819)
F-F Q5,Q6,Q7,P7 18720 (8491) 23880 (10832) 2175 (987)
G-E P8 20300 (9208) 24200 (10977) 1990 (903)
H-F P8,P9 23100 (10478) 28000 (12701) 2610 (1184)
J-J P8,P9 24000 (10886) 29100 (13200) 2550 (1157)
L-L P8,P9 27400 (12429) 33900 (15377) 3165 (1436)
K-K H9 28530 (12941) 36000 (16329) 2925 (1327)
K-K K1 31100 (14107) 36200 (16420) 3248 (1473)
K-O H9 34483 (15641) 44776 (20310) 3260 (1479)
M-M H9 34200 (15513) 43600 (19777) 3665 (1662)
M-M K1,K2 38300 (17373) 47100 (21364) 3665 (1662)
M-U K2 45178 (20493) 58017 (26316) 3540 (1606)
N-N K1,K2 40893 (18549) 50800 (23043) 4225 (1916)
N-N K3 48000 (21773) 54100 (24540) 4225 (1916)
P-P K1,K2 41500 (18824) 51900 (23542) 3855 (1749)
Q-Q K1,K2 45300 (20548) 56800 (25764) 4255 (1930)
Q-Q K3 46000 (20865) 60200 (27307) 4255 (1930)
R-R K3 52800 (23950) 70300 (31888) 4600 (2087)
R-R K4 53000 (24041) 70600 (32024) 4600 (2087)
S-S K4 59000 (26762) 76300 (34609) 4815 (2184)
S-V K4 60100 (27261) 81300 (36877) 5467 (2480)
X-T K4 59200 (26853) 80000 (36288) 5338 (2421)
X-X K4 66000 (29937) 87000 (39463) 5875 (2665)
W-W K7 79500 (36061) 104000 (47174) 8002 (3630)
Z-Y K7 95230 (43196) 123015 (55799) 7175 (3255)
Z-Z K7 80500 (36515) 105000 (47628) 6984 (3168)
1
Refrigerant charge quantity and weights will vary based on tube count.
SHELLS COMPRESSOR
SHIPPING WEIGHT
LBS. (KGS.)
OPERATING WEIGHT
LBS. (KGS.)
EST. REFRIGERANT
CHARGE LBS. (KGS.)
1
A-A Q3 12850 (5829) 14419 (6540) 695 (315)
C-C Q3, Q4 14570 (6609) 16848 (7642) 875 (397)
C-C Q5 15000 (6804) 17278 (7837) 875 (397)
D-D Q4 17000 (7711) 20051 (9095) 1180 (535)
D-D Q5 17410 (7897) 20461 (9281) 1180 (535)
E-E Q5,Q6,Q7,P7 18700 (8482) 21700 (9843) 1120 (508)
F-F Q5,Q6,Q7,P7 19220 (8718) 23142 (10497) 1415 (642)
G-E P8, P9 20640 (9362) 24036 (10903) 1320 (599)
H-F P8, P9 23540 (10678) 28083 (12738) 1775 (805)
I-K H9 28849 (13086) 34078 (15458) 1820 (826)
K-K H9 28850 (13086) 34079 (15458) 1820 (826)
I-K K1 31350 (14220) 35145 (15942) 1820 (826)
M-M K1,K2 34520 (15658) 46055 (20890) 2300 (1043)
N-N K1,K2 41273 (18721) 49605 (22501) 2650 (1202)
N-N K3 48380 (21945) 52905 (23998) 2650 (1202)
P-P K1,K2 41950 (19028) 51595 (23403) 3100 (1406)
Q-Q K1,K2 45800 (20775) 56545 (25649) 3500 (1588)
Q-Q K3 46500 (21092) 59945 (27191) 3500 (1588)
1
Refrigerant charge quantity and weights will vary based on tube count and conguration. Use for reference only.
TABLE 20 - APPROXIMATE UNIT WEIGHT INCLUDING MOTOR FOR FLOODED EVAPORATOR UNITS
TABLE 21 - APPROXIMATE UNIT WEIGHT INCLUDING MOTOR FOR HYBRID FALLING FILM EVAPORATOR
UNITS
Weights