JOHNSON CONTROLS
FORM 160.75-EG1 (519)
68
Application Data (Cont'd)
TABLE 16 - LOW VOLTAGE SOLID-STATE STARTER MODELS
SSS-
MAXIMUM
LRA
MINIMUM
FLA
MAXIMUM
FLA
RATED
VOLTAGE
ACTUAL
VOLTAGE
PHASE HZ
7L-46B 1556 35 260 460 440/460/480 3 60
7L-40B 1556 35 260 380 380 3 60
7L-50B 1556 35 260 400 380/440/415 3 50
7L-58B 1556 35 260 575 575/600 3 60
14L-17B 3111 65 510 200 200/208 3 60
14L-28B 3111 65 510 230 230/240 3 60
14L-40B 3111 65 510 380 380 3 60
14L-46B 3111 65 510 460 440/460/480 3 60
14L-50B 3111 65 510 400 380/400/415 3 50
14L-58B 3111 65 510 575 575/600 3 60
26L-17B 5780 125 850 200 200/208 3 60
26L-28B 5780 125 850 230 230/240 3 60
26L-40B 5780 125 850 380 380 3 60
26L-46B 5780 125 850 460 440/460/480 3 60
26L-50B 5780 125 850 400 380/400/415 3 50
26L-58B 5780 125 850 575 575/600 3 60
33L-17B 7333 215 1050 200 200/240 3 60
33L-40B 7333 215 1050 380 380 3 60
33L-46B 7333 215 1050 230 230/240 3 60
33L-50B 7333 215 1050 400 380/400/415 3 50
33L-58B 7333 215 1050 460 440/460/480 3 60