JOHNSON CONTROLS
FORM 160.75-EG1 (519)
62
Application Data (Cont'd)
NOTES:
1. High voltage and special motor designs may not meet efciency, power factor or amperes values shown for standard motors.
2. Min. reduced voltage tap 80%.
TABLE 11 - 60 HZ ELECTRICAL DATA - PREMIUM EFFICIENCY
MOTOR CODE EF EG EH EJ EK EL EM EN EP ER ES ET EU EV
SHAFT HP (MAX) 154 177 201 237 270 302 327 351 385 424 468 503 554 608
INPUT KW (MAX) 122 139 158 185 211 236 256 274 300 330 363 390 431 473
F.L. EFF. - % 94.5 95 95 95.4 95.4 95.4 95.4 95.4 95.8 95.8 96.2 96.2 95.8 95.8
F.L. POWER
FACTOR
0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88
VOLTS AMPERES (MAXIMUM)
200
FLA 399 456 518 608 692 774 838 900 983 1083 1190 - - -
LRA 2815 3128 3128 3979 4550 4900 5635 5865 6686 7350 7935 - - -
208
FLA 383 438 498 584 666 745 806 865 945 1041 1144 - - -
LRA 2928 3235 3235 4138 4732 5096 5860 6100 6953 7644 8252 - - -
230
FLA 347 396 450 528 602 673 729 783 855 941 1035 1112 - -
LRA 2598 2720 2865 3460 3788 4260 4900 5162 5814 6200 6900 8513 - -
240
FLA 332 380 431 506 577 645 699 750 819 902 992 1066 - -
LRA 2711 2838 2990 3610 3953 4445 5113 5386 6067 6470 7200 8883 - -
380
FLA 210 240 272 320 364 408 441 474 517 570 626 673 745 817
LRA 1482 1646 1730 2153 2500 2578 2966 3254 3637 3810 4179 4480 4671 5326
416
FLA 192 219 249 292 333 372 403 433 473 521 572 615 680 746
LRA 1385 1504 1638 1967 2190 2356 2709 2976 3536 3637 3815 3826 4270 5418
440
FLA 181 207 235 276 315 352 381 409 447 492 541 581 643 706
LRA 1177 1301 1320 1655 1865 2037 2485 2485 2976 2976 3300 3348 3644 4687
460
FLA 173 198 225 264 301 337 365 391 427 471 517 556 615 675
LRA 1230 1360 1380 1730 1950 2130 2598 2598 3111 3111 3450 3500 3810 4900
480
FLA 166 190 216 253 288 323 349 375 410 451 496 533 589 647
LRA 1283 1419 1440 1805 2035 2223 2711 2711 3246 3246 3600 3652 3976 5113
575
FLA 139 159 180 211 241 269 292 313 342 377 414 445 492 540
LRA 979 1088 1100 1384 1556 1704 1960 2066 2326 2413 2760 2960 3089 3550
600
FLA 133 152 173 203 231 258 279 300 328 361 397 426 472 517
LRA 1021 1135 1148 1444 1624 1778 2045 2156 2427 2518 2880 3089 3223 3704
NOTE: These motors are designed to meet or exceed NEMA Premium (MG1-2006) and European IE2 efciency requirements.
TABLE 12 - 50 HZ ELECTRICAL DATA - PREMIUM EFFICIENCY
MOTOR CODE 5EC 5ED 5EE 5EF 5EG 5EH 5EI 5EJ 5EK 5EL 5EM 5EN 5EO
SHAFT HP (MAX) 148 168 198 225 252 272 292 321 353 390 419 462 507
INPUT KW (MAX) 117 133 156 177 198 214 229 252 277 305 328 361 396
F.L. EFF. - % 94.3 94.5 94.7 94.9 95 95 95 95 95 95.4 95.4 95.4 95.4
F.L. POWER
FACTOR
0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88
VOLTS AMPERES (MAXIMUM)
346
FLA 222 251 296 335 375 405 435 478 525 578 621 685 751
LRA 1521 1721 1790 2208 2467 2706 2840 3081 3350 3706 3810 4177 5150
380
FLA 202 229 269 305 342 369 396 435 478 526 565 623 684
LRA 1385 1385 1640 1890 2144 2464 2590 2806 3050 3375 3700 3810 4690
400
FLA 192 217 256 290 324 350 376 413 454 500 537 592 650
LRA 1458 1458 1726 1989 2257 2594 2726 2954 3211 3553 3895 4011 4937
415
FLA 185 210 246 280 313 338 362 398 438 482 518 571 627
LRA 1283 1385 1502 1700 2031 2175 2366 2569 2794 3088 3402 3478 4027