FORM 160.75-EG1 (519)
JOHNSON CONTROLS
57
HYBRID FALLING FILM EVAPORATORS
MODEL
1 PASS 2 PASS 3 PASS
MIN MAX MIN MAX MIN MAX
QD
3199
(202)
12794
(807)
1598
(101)
4526
(286)
1065
(67)
3042
(192)
QF
3680
(232)
14722
(929)
1839
(116)
5268
(332)
1227
(77)
3479
(220)
QH
1902
(120)
7608
(480)
951
(60)
2799
(177)
Q5
2580
(163)
10319
(651)
1287
(81)
4734
(299)
Q7
3027
(191)
12107
(764)
1510
(95)
5456
(344)
1009
(64)
3716
(234)
TABLE 7 - HYBRID FALLING FILM EVAPORATOR WATER FLOW RATE LIMITS GPM (L/S) – BASED UPON
STANDARD TUBES @ DESIGN FULL LOAD CONDITIONS (CONT'D)
Application Data (Cont'd)