FORM 160.75-EG1 (519)
JOHNSON CONTROLS
79
Dimensions (Cont'd)
COMPACT WATER BOXES - 150 PSI ROUND
EVAPORATOR
SHELL CODE
NOZZLE PIPE SIZE(IN)
NO. OF PASSES
EVAPORATOR NOZZLE DIMENSIONS
C
1-PASS 2-PASS 3-PASS
1 2 3 AA5 BB5 DD5 BB5 DD5
A 8 6 4
1' 3-1/2"
(394)
1' 10"
(559)
1' 2"
(356)
2' 6"
(762)
1' 2"
(356)
2' 6"
(762)
C,D 10 8 6
1' 5-1/2"
(445)
2' 0"
(610)
1' 3"
(381)
2' 9"
(838)
1' 3"
(381)
2' 9"
(838)
E,F 14 10
8
1' 7"
(483)
2' 2"
(660)
1' 4"
(406)
3' 0"
(914)
1' 4"
(406)
3' 0"
(914)
G,H 14 10
8
2' 0"
(610)
2' 3-1/2"
(699)
1' 3-1/2"
(394)
3' 3-1/2"
(1003)
1' 3-1/2"
(394)
3' 3-1/2"
(1003)
I, J, K, L 16 12 10
2' 1-1/4"
(641)
2' 6"
(762)
1' 5"
(432)
3' 7"
(1092)
1' 5"
(432)
3' 7"
(1092)
EVAPORATORS COMPACT WATER BOXES – A THROUGH L EVAPORATORS
NOTES:
1. All dimensions are ft-inches (mm).
2. All dimensions are approximate. Certied dimensions are available on request.
3. For all waterboxes (compact boxes shown above), determine overall unit length by adding waterbox depth to tube sheet length.
4. Water nozzles can be located on either end of unit. Add 1/2" (12 mm) to nozzle length for anges connections.
5. To determine overall height, add dimension "M" on page 76 for the appropriate isolator type.
6. Use of motors with motor hoods may increase overall unit dimensions.