EasyManua.ls Logo

York YMC2 - Page 139

York YMC2
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
139
SECTION 6 - PRINTING
FORM 160.84-OM1
ISSUE DATE: 9/21/2017
6
FIGURE 53 - SAMPLE PRINTOUT (STATUS OR HISTORY) (CONT'D)
Variable Speed Drive – Fault Snapshot
------------------------------------------------------
VSD Output Voltage = 0 V
VSD Output Frequency = 0.00 Hz
Input Power = 0 kW
L1 Voltage Total Harmonic Distortion = 8.0 %
L2 Voltage Total Harmonic Distortion = 8.0 %
L3 Voltage Total Harmonic Distortion = 3.0 %
L1 Input Current Total Demand Distortion = 0.0 %
L2 Input Current Total Demand Distortion = 0.0 %
L3 Input Current Total Demand Distortion = 0.0 %
Input KVA = 1 kVA
VSD Control State = Run
VSD Inverter State = Run
Phase Rotation = ABC
Precharge Active = On
Precharge Complete = False
DC Bus Regulating = Off
DC Bus Voltage = 696 V
Input Current Limit = Off
Cooling System = On
L1 Input Voltage (peak) = 698 V
L2 Input Voltage (Peak) = 707 V
L3 Input Voltage (Peak) = 696 V
L1 Input Voltage (RMS) = 698 V
L2 Input Voltage (RMS) = 707 V
L3 Input Voltage (RMS) = 696 V
L1 Input Current (Peak) = 1 A
L2 Input Current (Peak) = 1 A
L3 Input Current (Peak) = 0 A
L1 Input Current (RMS) = 1 A
L2 Input Current (RMS) = 1 A
L3 Input Current (RMS) = 0 A
Phase A Output Voltage (RMS) = 0 V
Phase B Output Voltage (RMS) = 0 V
Phase C Output Voltage (RMS) = 0 V
Phase A Output Current (Peak) = 0 A
Phase B Output Current (Peak) = 0 A
Phase C Output Current (Peak) = 0 A
Phase A Output Current (RMS) = 0 A
Phase B Output Current (RMS) = 0 A
Phase C Output Current (RMS) = 0 A
Phase A Rectier Baseplate Temperature = 81 ~F
Phase B Rectier Baseplate Temperature = 80 ~F
Phase C Rectier Baseplate Temperature = 77 ~F
Phase A Inverter Baseplate Temperature = 87 ~F
Phase B Inverter Baseplate Temperature = 82 ~F
Phase C Inverter Baseplate Temperature = 80 ~F
Internal Ambient Temperature 1 = 77 ~F
Internal Ambient Temperature 2 = 77 ~F
Test Mode = Disabled
Motor Monitoring
-----------------------------------------------------
Motor Winding Phase A Temp Z1 End = 71 ~F
Motor Winding Phase B Temp Z1 End = 71 ~F
Motor Winding Phase C Temp Z1 End = 71 ~F
Motor Winding Phase A Temp Z2 End = 71 ~F
Motor Winding Phase B Temp Z2 End = 71 ~F
Motor Winding Phase C Temp Z2 End = 71 ~F
Average Winding Temperature = 71.0 ~F
Estimated Rotor Temperature = 123.4 ~F
Motor Housing Temperature = 71 ~F
Motor Housing Temperature Setpoint = 71 ~F
Motor Winding Temperature Setpoint = 121 ~F
Ambient Dew Point Temperature = 71 ~F
(when Dew Point Enabled)
Motor Cooling Valve Command = 25.0 %
Motor Cooling Control State = Inactive
Capacity Control
-----------------------------------------------------
Control State = Inactive
Load Limit = Inactive
VSD Frequency Command = 0.00 Hz
VSD Output Frequency = 0.00 Hz
VSD Control Mode = Auto
Active Anti-Surge Minimum Frequency = 0.00 Hz
Anti-Surge Minimum Frequency = 0.00 Hz
Anti-Surge Transient Offset = 0.00 Hz
VGD Command = 25.00 %
VGD Position = 25.00 %
VGD Control Mode = Auto
HGBP Command = 25.0 %
(when HGBP enabled)
HGBP Control Mode = Auto
(when HGBP enabled)
Head Pressure = 0.0 PSID
Evaporator Pressure = 46.40 PSIG
Condenser Pressure = 68.30 PSIG
Leaving Chilled Liquid Temperature = 44.80 ~F
Magnetic Bearing Controller
-----------------------------------------------------
MBC Control Mode = Auto
MBC Levitation Command = On
MBC Rotation Command = On
Levitation Mode = On
Rotation Mode = On
MBC Alarm = On
MBC Alive = On
Rotation Allowed = On
MBC Fault = On
Motor Speed = 44 Hz
MBC Input Voltage = 150 V
V13 Position = 14 ~m
W13 Position = 13 ~m
V24 Position = 13 ~m
W24 Position = 12 ~m
Z12 Position = 2 ~m
V1 Current = 1.803 A
V2 Current = 1.772 A
V3 Current = 0.878 A
V4 Current = 0.972 A
W1 Current = 1.992 A
W2 Current = 1.788 A
W3 Current = 0.721 A
W4 Current = 0.894 A
Z1 Current = 1.082 A
Z2 Current = 1.443 A
Rotor Elongation = 102 ~m
VW13 Soft Landing Counter = 0
VW24 Soft Landing Counter = 0
Z12 Soft Landing Counter = 0
VW13 Hard Landing Counter = 0
VW24 Hard Landing Counter = 0
Z12 Hard Landing Counter = 0
Power Fail Landing Counter = 0
A13 Unbalance = 0 ~m
B13 Unbalance = 0 ~m
A24 Unbalance = 0 ~m
B24 Unbalance = 0 ~m
Az Vibration = 0 ~m
Bz Vibration = 0 ~m
Z1 Temperature = 91 ~F
Z2 Temperature = 77 ~F
MBC Amplier Temp = 88 ~F
MBC Operation Time = 3 Days
SDR Counter = 1
First Alarm Code = 16
Active Parameter Set = 0
ID Faults = 0
Checksum Errors = 0
Error Packets = 0
Timeout Faults = 0
Power Panel
-----------------------------------------------------
Control Voltage = On
Power Loss Time = 15 Sec
UPS Line / Charging = On
UPS Inverter = Off
UPS Fault = Off
UPS Battery V+ = On
UPS Battery Voltage = 12.0 V
UPS Inverter Enable = On
Power Panel Temperature = 79.0 ~F
Power Panel Cooling System Run = On
Manual Power Panel Cooling = Disabled
Line Low Battery Voltage Offset = 0.0 V
Inverter Low Battery Voltage Threshold = 11.0 V
Battery Voltage Faults = Enabled