JOHNSON CONTROLS
54
FORM 160.84-OM1
ISSUE DATE: 9/21/2017
SECTION 3 - OPTIVIEW™ CONTROL CENTER FUNCTIONS AND NAVIGATION
OVERVIEW
This screen displays information pertaining to the Vari-
able Speed Drive (VSD).
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
VSD Fault (LED)
Indicates the VSD is reporting a fault over the commu-
nications link or by logic low at the hardwired digital
input.
Input % Full Load Amps
Displays the input current as a percentage of the job
Full Load Amps (FLA) value, based on the highest
phase.
Input Current Limit Setpoint
Displays the input current limit value in use. This val-
ue could come from a 0-20mA, 4-20mA, 0-10VDC or
2-10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, SC-Equip Gateway interface
in BAS (ISN) mode, or a locally programmed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
VSD Output Voltage
Displays the output voltage measured to the motor.
VSD Output Frequency
Displays the present output frequency to the motor.
Max Chiller Frequency
Displays the maximum value that the Output frequen-
cy is limited to for the chiller, based on configuration.
Input Power
Displays the total input Kilowatts measured by the
VSD.
Input kW Hours
Displays the cumulative amount of kilowatts used over
time as the VSD motor controller operates.
VARIABLE SPEED DRIVE SCREEN
LD17932a
FIGURE 17 - VARIABLE SPEED DRIVE SCREEN