EasyManua.ls Logo

York YMC2 - Page 144

York YMC2
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
144
FORM 160.84-OM1
ISSUE DATE: 9/21/2017
SECTION 6 - PRINTING
YORK TREND
CHILLER ID 163
© 1997 – 2000 YORK INTERNATIONAL CORPORATION
MON 09 OCT 2000 3:33:47 PM
DATA 1: LEAVING CHILLED LIQUID TEMPERATURE
DATA 2: RETURN CHILLED LIQUID TEMPERATURE
DATA 3: EVAPORATOR PRESSURE
DATA 4: LEAVING CONDENSER LIQUID TEMPERATURE
DATA 5: RETURN CONDENSER LIQUID TEMPERATURE
DATA 6: CONDENSER PRESSURE
TIME DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6
3:33:47 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.0 °F 120.0 PSIG
3:33:48 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.0 °F 120.0 PSIG
3:33:49 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.0 °F 120.0 PSIG
3:33:50 PM 45.5 °F 55.0 °F 39.0 PSIG 95.0 °F 85.3 °F 120.1 PSIG
3:33:51 PM 45.5 °F 55.2 °F 39.1 PSIG 95.1 °F 85.4 °F 120.2 PSIG
FIGURE 58 - SAMPLE PRINTOUT (TREND DATA
NEW OR EXISTING POINTS)
FIGURE 57 - SAMPLE PRINTOUT (SECURITY LOG
REPORT)
YORK SETPOINT CHANGE LOG
CHILLER ID 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Fri 05 Oct 2001 4:48:04 PM
Log Entry 1 Evaporator - Leaving Chilled Local Setpoint
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 4:23:49 PM
Access Level = Service
User Id = 4268
Old Value = 46.5 ~F
New Value = 48.0 ~F
Log Entry 2 Condenser - High Pressure Warning Threshold
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 1:36:12 PM
Access Level = Service
User Id = 4268
Old Value = 162.5 Psig
New Value = 225.0 Psig
Log Entry 3 Condenser - Drop Leg
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 1:36:02 PM
Access Level = Service
User Id = 4268
Old Value = Disabled
New Value = Enabled
Log Entry 4 Evaporator - Refrigerant
---------------------------------------------------------------------------------
Date = 05 Oct 2001
Time = 1:35:48 PM
Access Level = Service
User Id = 4268
Old Value = Disabled
New Value = Enabled
FIGURE 59 - SAMPLE PRINTOUT (CUSTOM
SCREEN REPORT)
YORK CUSTOM VIEW
CHILLER ID 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Mon 21 Jun 1999 1:28:25 PM
Leaving Chilled Liquid Temperature = 45.0 ~F
Return Chilled Liquid Temperature = 55.0 ~F
Leaving Condenser Liquid Temperature = 95.0 ~F
Return Condenser Liquid Temperature = 85.0 ~F
Evaporator Saturation Temperature = 41.0 ~F
Condenser Saturation Temperature = 78.5 ~F
Evaporator Pressure = 70.0 Psig
Condenser Pressure = 140.0 Psig
Oil Pressure = 45.0 Psid
% Full Load Amps = 50 %

Table of Contents

Other manuals for York YMC2

Related product manuals