SECTION 4 - INSTALLATION
Form 201.47-ICOM1
Issue date: 17/11/2022
EBM CONDENSER FANS
FIELD WIRING LUGS TERMINAL BLOCK CIRCUIT BREAKER NON-FUSED DIS-
CONNECT SWITCH
YVAA-B MODEL EVAP INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
SINGLE POINT WIRING
0309/1089 2205 200 60
230 60
380 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
400 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
400 50 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
575 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
4 #2 ~ 600
kcmil
0334/1174 2205 200 60
230 60
380 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
400 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
400 50 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
575 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
4 #2 ~ 600
kcmil
0361/1271 2205/2605 200 60
230 60
380 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 4/0 ~ 500
kcmil
400 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 4/0 ~ 500
kcmil
400 50 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 4/0 ~ 500
kcmil
460 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 4/0 ~ 500
kcmil
575 60 3 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
2 2/0 ~ 500
kcmil
Table 4 - Electrical lug data (cont'd)