SECTION 4 - INSTALLATION
JOHNSON CONTROLS
45
Form 201.47-ICOM1
Issue date: 17/11/2022
4
Table 4 - Electrical lug data
STANDARD 2HP (with & Without VSD) CONDENSER FANS
FIELD WIRING LUGS TERMINAL BLOCK CIRCUIT BREAKER NON-FUSED DIS-
CONNECT SWITCH
YVAA-B MODEL EVAP INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
SINGLE POINT WIRING
YVAA0161/0571 2004 200 60 4 #2 – 600
kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 2 #2 – 600
kcmil
2 2/0 ~ 500
kcmil
2 #2 – 600
kcmil
400 50 2 #2 – 600
kcmil
2 2/0 ~ 500
kcmil
2 #2 – 600
kcmil
460 60 2 #2 – 600
kcmil
2 2/0 ~ 500
kcmil
2 #2 – 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
2 #2 ~ 600
kcmil
YVAA0201/0701 2004 200 60 4 #2 – 600
kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 – 600
kcmil
400 50 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 – 600
kcmil
460 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
3 #2 – 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
2 #2 ~ 600
kcmil
YVAA0166/0586 2004 200 60 4 #2 – 600
kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 2 #2 – 600
kcmil
2 2/0 ~ 500
kcmil
2 #2 – 600
kcmil
400 50 2 #2 – 600
kcmil
2 2/0 ~ 500
kcmil
2 #2 – 600
kcmil
460 60 2 #2 – 600
kcmil
2 2/0 ~ 500
kcmil
2 #2 – 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
2 #2 ~ 600
kcmil
YVAA0211/0741 2004 200 60 4 #2 – 600
kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
3 #2 ~ 600
kcmil
400 50 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
3 #2 ~ 600
kcmil
460 60 2 #2 – 600
kcmil
2 2/0 ~ 500
kcmil
2 #2 – 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
2 #2 ~ 600
kcmil