2.3 PROTECTION FEATURES
- Battery polarity inversion
It is necessary to fit a MAIN CONTACTOR to protect the inverter against reverse battery
polarity and for safety reasons.
- Connection Errors
All inputs are protected against connection errors.
- Thermal protection
If the chopper temperature exceeds 78°C, the maximum current is reduced in
proportion to the thermal increase. The temperature can never exceeds 100°C.
- External agents
The inverter is protected against dust and the spray of liquid to a degree of
protection meeting IP54.
- Protection against uncontrolled movements
The main contactor will not close if:
- The Power unit is not functioning.
- The Logic is not functioning perfectly.
- the output voltage of the accelerator does not fall below the minimum voltage value
stored, with 1V added.
- Running microswitch in closed position.
- Low battery charge
when the battery charge is low, the maximum current is reduced to the half of the maxi-
mum current programmed.
- Protection against accidental Start up
A precise sequence of operations are necessary before the machine will start.
Operation cannot begin if these operations are not carried out correctly.
Requests for drive, must be made after closing the key switch.