12 Troubleshooting an measures
Error
Cause
Remedy
8fail8 as self-test result
Self-test failed
Check all measured voltages, check
Feedback contact (see 8Err78)
8EEEE8 or 8-EEE8
appears in the display
Measurement is above/below
range
Measured voltage, frequency or the
vector surge is too large or too small;
comply with measurement range
8Err58 appears in the
display
Error internal interface
Reset interrupt control voltage for
>5s
8Err78 also appears in
the display after 2
automatic reconnection
attempts, LED K1 flashes,
K2 is released
Error when off the section switch,
section switch connected wrong,
faulty or operated from a third
party switch
Feedback contacts not connected
Set - 8rel .8 8trel.8 8 off8
Feedback contacts connected
- Check for correct connection
- Set turn-on time of section switch
under 8trel.8
- Do a reset interrupt control voltage
for >5s
8Err78 LED K1 flashes
und K2 is operating
Error when off the section switch
- Check the connection
- Check for broken section switch
- Do a reset interrupt control voltage
for >5s
8Err88 appears in the
display
Hysteresis error
Upper threshold value must be higher
than the lower threshold value, check
the threshold values
8Err98 appears in the
display
Parameter error
Reset to factory settings, see “Program
setup”
A time expires in the
display
Always when an OFF-delay time
8dof 8 is running, it is counted
down in the display (shortest one
first)
Wait until the time has expired
(depending on the setting, several
times may elapse one after the other)
Device cannot be
configured / only the limits
can be configured
Code lock / Sealing activated
If there are any problems with the code
lock (pin forgotten), the lock can be
switched off and the pin can be reset
to 504 by keeping the Set key pressed
while switching on the mains until
8Code8 / 8 off8 appears in the
display.
Implausible voltage values
Pr selected with N, but N not
connected
Select Pr without N or connect N
8Loc 8 appears in the
display
Seal is active
See Sealing
8Code8 appears in the
display
Code lock is active
See „Code lock“
8stby8 appears in the
display
Standby mode, E1-E2 closed
Check parameter 8 vsr.8