106
COMMAND
NAME
DESCRIPTION No.
COMMAND SYNTAX
Command Argument 1 Argument 2 Argument 3 Argument 4 Response
Program
Set Point
Sets/Reads Program Set
Point parameters
31 PS
C
Run / Stop Program
Set Point
R - Run PSP
S - Sto PSP
No Argument
(Ret. Current settings)
PSC:R,11 (PSP is running
and current step is 11)
<value> R - Run
S - Stop PSP
PSC:<value>
PSC:S (to stop PSP)
<value>
[1-16] step number
<value> R-Run
S - Stop PSP
PSC:<value>,<value>
PSC:5,R (to start from s. 5)
M
Read/Change Device
PSP Mode
<New Value>
E or D
PSM:<value>
Example: PSM:D
No Argument (Ret.
Current settings)
PSM:<value>
Example: PSM:D
L
Read/Change Device
PSP Loop Mode
<New Value>
E or D
PSL:<value>
Example: PSL:D
No Argument (Ret.
Current settings)
PSL:<value>
Example: PSL:D
P
Read/Change Device PSP
Step Parameters Read:
only one argument is
required. Change: all 3
arguments are required.
<Step Number>
[1-16]
No Argument
(Ret. Current
settings)
PSP<step>:<SP>,<Time>
Example: PSP02: 50.0,25
<Step Number>
[1-16]
<Set Point>
[0-100%FS]
<Time>
[0-86400 s.]
PSP<step>:<SP>,<Time>
Example: PSP02: 50.0,25
A
Read/Change Device
PSP Mask Register
No Argument
(read current PSP
Mask register)
PSA:0xFFFF 0x00FF –
screen mask (8 bits wide).
Set bit – Step Enabled
Clear bit – Step Disabled
<Value> 0x0000
- 0xFFFF
Set new value NOTE: all
6 characters are required
PSA:0xFFFE