266CRx, 266JRx, 266CSx, 266JSx | OI/266CXX/266JXX/HART-EN Rev. B 65
Error code Displayed message Possible cause Recommended measure Transmitter
reaction
M018.038
PILD Output Both impulse lines between the measuring
cell and the process are either clogged or
closed by valves.
Check valves and impulse line. If required,
clean the impulse lines and start PILD
training.
None
The impulse line between the pressure
measuring cell and the process is either
clogged on the high pressure side or closed
by valves.
The impulse line between the pressure
measuring cell and the process is either
clogged on the low pressure side or closed
by valves.
One of the impulse lines between the
pressure measuring cell and the process is
either clogged or closed by valves.
M020.042
Replace Info The electronics or the measuring cell have
been replaced, but replacement mode has
not been executed.
Execute replacement mode: Place switch
SW 1 of the electronics in position 1 =
activate replacement mode. With switch
SW 2 select whether measuring cell or the
electronics have been replaced. Switch
device off and on. Return switch SW 1 of
the electronics to position 0.
None
The electronics or the measuring cell has
been replaced and replacement mode for a
new measuring cell must be executed.
Execute replacement mode: Only the data
of the electronics can be copied into the
measuring cell. Place switch SW 1 on (1) to
activate replacement mode 1 - with switch
SW2 select new measuring cell (1). Switch
device off and on. Place switch SW 1 on (0)
to deactivate replacement mode.
The electronics or the measuring cell has
been replaced, replacement mode has been
activated, but in the wrong direction (SW 2 =
0).
Change replacement direction (if possible).
Switch SW 1 is already in position (1),
replacement mode is activated. Switch SW
2 to position (1) for “new measuring cell”.
Switch device off and on. Place switch SW
1 is position (0) to deactivate replacement
mode.