Figure 12: Drill plan for the LHMI
A
220 mm 1 LHMI outline
B M3 2 Surface coating on rear side of panel must be removed ∅15 mm
C 177 mm 3 Hole for GND connection
D 162 mm 4 Hole for cable from IED to LHMI
E ∅6.5 mm
F ∅20 mm
G 78 mm
H 7.5 mm
I 38 mm
J 128 mm
K 33 mm
L 18.5 mm
2. Thread the four holes for the M3 screws.
3. Remove surface coating from the rear side of the panel for the GND screw.
4. Draw the LHMI cable through the hole for cable from IED to LHMI.
5. Connect the cable to the LHMI.
6. Mount the external LHMI display using four M3 screws.
7. Tighten the four M3 screws.
8. Ground the LHMI.