110kV Busbar
200/1
35/ 0,1kV
35kV Busbar
500/5
P Q
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
U
L1L2
IEC09000040-1-en.vsd
IED
IEC09000040-1-EN V1 EN-US
Figure 99: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 99, it is
necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRef
(see Section “Setting of the phase reference channel”) data using PCM600 for
analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table
23:
Section 10 1MRK 511 423-UEN A
Monitoring
202 Bay control REC650 2.2 IEC
Application manual