ACH580 Installation, Operation and Maintenance Manual 25
ACH580-01 Installation
UL (NEC) ratings at U
N
= 575 V
Definitions
ACH580-01-180A-4 180 2346 265 R7
ACH580-01-240A-4 240 3336 324 R8
ACH580-01-302A-4 302 4836 677 R9
ACH580-01-361A-4 361 6036 677 R9
ACH580-01-414A-4 414 6036 677 R9
Type
Output ratings
Heat
dissipation
Air
flow
Frame
size
A W ft
3
/min
ACH580-01-02A7-6 2.7 66 59 R2
ACH580-01-03A9-6 3.9 84 59 R2
ACH580-01-06A1-6 6.1 133 59 R2
ACH580-01-09A0-6 9 174 59 R2
ACH580-01-011A-6 11 228 59 R2
ACH580-01-017A-6 17 322 59 R2
ACH580-01-022A-6 22 430 105 R3
ACH580-01-027A-6 27 525 105 R3
ACH580-01-032A-6 32 619 105 R3
ACH580-01-041A-6 41 835 82 R5
ACH580-01-052A-6 52 1024 82 R5
ACH580-01-062A-6 62 1240 82 R5
ACH580-01-077A-6 77 1510 82 R5
ACH580-01-099A-6 99 2061 265 R7
ACH580-01-125A-6 125 2466 265 R7
ACH580-01-144A-6 144 3006 324 R8
ACH580-01-192A-6 156 4086 677 R9
ACH580-01-242A-6 242 4896 677 R9
ACH580-01-271A-6 271 4896 677 R9
U
N
Output voltage of the drive.
I Continuous rms output current, allowing 110% overload for 1 minute every 10 minutes.
P Typical motor power
Type
Output ratings
Heat
dissipation
Air
flow
Frame
size
A W ft
3
/min
ACH580_Inst_Op_Maint_Rev G.book Page 25