ACH580-01 Installation
Fuses
Note: The UL listed fuses in the table are the required branch circuit protection.
Fuses are to be provided as part of the installation.
Fuses are not included in the purchased drive and must be provided by others.
Fuses with higher current rating than specified must not be used.
Fuses with lower current rating than specified may be used if they are of the same
class and voltage rating. It is the user's responsibility to verify that lower current
rated fuses are compliant with local regulations and appropriate for the
application.
Drive fuses must be used to maintain the drive UL listing. Additional protection
can be used. Refer to local codes and regulations.
208...240 volt, fuse requirements
ACH580-01-
Input
curren
t
A
UL
Maximu
m
current
Voltag
e
rating
Bussmann type 1
UL class
3-phase UN = 208 V
04A6-2 4.6 15 600 KTK-R-15 or JJS-15 CC or T
06A6-2 6.6 15 600 KTK-R-15 or JJS-15 CC or T
07A5-2 7.5 15 600 KTK-R-15 or JJS-15 CC or T
10A6-2 10.6 15 600 KTK-R-15 or JJS-15 CC or T
017A-2 16.7 30 600 KTK-R-30 or JJS-30 CC or T
024A-2 24.2 40 600 JJS-40 T
031A-2 30.8 40 600 JJS-40 T
046A-2 46.2 80 600 JJS-80 T
059A-2 59.4 80 600 JJS-80 T
075A-2 74.8 100 600 JJS-100 T
088A-2 88 150 600 JJS-150 T
114A-2 114 150 600 JJS-150 T
144A-2 143 200 600 JJS-200 T
169A-2 169 250 600 JJS-250 T
211A-2 211 300 600 JJS-300 T
273A-2 273 400 600 JJS-400 T
1) ABB does not require Bussmann brand fuses. Fuses which meet the
appropriate UL class type, current rating, and are rated at 600V, 200 kA may be
used.