104 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
N2 binary input objects – Drive
The following table lists the N2 Binary Input objects defined for the ACH580 drive.
AI14 PRC PID DEVIATION 40.99 0.1 % 0…100
AI15 EXT PID FEEDBACK Derived value 0.1 % 0…100
AI16 EXT PID DEVIATION Derived value 0.1 % 0…100
AI17 LAST FAULT Derived value 1 fault code
AI18 PREV FAULT Derived value 1 fault code
AI19 OLDEST FAULT Derived value 1 fault code
AI20 AI 1 ACTUAL 12.101 0.1 % 0…100
AI21 AI 2 ACTUAL 12.102 0.1 % 0…100
AI22 AO 1 ACTUAL 13.11 0.1 mA 0…20
AI23 AO 2 ACTUAL 13.21 0.1 mA 0…20
AI24 MOTOR TEMP Derived value 1
°C 0…200
1) Rated Speed Is A Percent Of Maximum Frequency (Parameter 2008) If The Drive Is In Scalar
Mode, And Is A Percent Of Maximum Speed (Parameter 2002) In Speed Mode.
N2 Binary Inputs:
Number Object Drive Parameter Range
BI1 STOP/RUN Status Word, BIT2 0 = Stop, 1 = Drive Running
BI2 FORWARD/REVERSE Status Word, BIT11 0 = Forward, 1 = Reverse
BI3 FAULT STATUS Status Word, BIT15 0 = OK, 1 = Drive Fault
BI4 RELAY 1 STATUS 10.21, BIT0 0 = Off, 1 = On
BI5 RELAY 2 STATUS 10.21, BIT1 0 = Off, 1 = On
BI6 RELAY 3 STATUS 10.21, BIT2 0 = Off, 1 = On
BI7 RELAY 4 STATUS 15.04, BIT0 0 = Off, 1 = On
BI8 RELAY 5 STATUS 15.04, BIT1 0 = Off, 1 = On
BI9 DIGITAL OUT 1 STATUS 15.04, BIT5 0 = Off, 1 = On
BI10 INPUT 1 STATUS 10.02, BIT0 0 = Off, 1 = On
BI11 INPUT 2 STATUS 10.02, BIT1 0 = Off, 1 = On
BI12 INPUT 3 STATUS 10.02, BIT2 0 = Off, 1 = On
BI13 INPUT 4 STATUS 10.02, BIT3 0 = Off, 1 = On
BI14 INPUT 5 STATUS 0119 (bit mask 02) 0 = Off, 1 = On
BI15 INPUT 6 STATUS 10.02, BIT5 0 = Off, 1 = On
BI16 EXTERNAL 2 SELECT DCU status word, BIT14 0 = EXT1 = EXT2
BI17 HAND/AUTO DCU status word, BIT12 0 = AUTO, 1 = HAND
BI18 WARNING DCU status word, BIT16 0 = OK, 1 = WARNING
BI20 DRIVE READY DCU status word, BIT0 0 = Not Ready, 1 = Ready
BI21 AT SETPOINT DCU status word, BIT7 0 = No, 1 = At Setpoint
N2 Analog Inputs:
Number Object