ACH580 E-Clipse bypass and packaged drive user manual 105
Embedded fieldbus
N2 analog output objects – Drive
The following table lists the N2 Analog Output objects defined for the ACH580 drive.
BI22 RUN PERMISSIVES DCU status word, BIT1 0 = Not Enabled, 1 = Enabled
BI23 N2 LOCAL MODE DCU status word, BIT13 0 = Auto, 1 = N2 Local
BI24 N2 CONTROL SRC DCU status word, BIT26 0 = No, 1 = Yes
BI25 N2 REF1 SRC DCU status word, BIT27 0 = No, 1 = Yes
BI26 N2 REF2 SRC DCU status word, BIT28 0 = No, 1 = Yes
N2 Analog Outputs:
Number Object
Drive
Parameter
Resolution Units Range
AO1 REFERENCE 1 Reference 1 0.1 % 0…100
AO2 REFERENCE 2 Reference 2 0.1 % 0…100
AO3 ACCEL TIME 1 Derived value 0.1 s 0.1…1800
AO4 DECEL TIME 1 Derived value 0.1 s 0.1…1800
AO5 CURRENT LIMIT 30.17 0.1 A 0…1.3•I
2n
AO6 PID1-CONT GAIN 40.32 0.1 % 0.1…100
AO7 PID1-CONT I-TIME 40.33 0.1 s 0.1…600
AO8 PID1-CONT D-TIME 40.34 0.1 s 0…10
AO9 PID1-CONT D FILTER 40.35 0.1 s 0…10
AO10 PID2-CONT GAIN 41.32 0.1 % 0.1…100
AO11 PID2-CONT I-TIME 41.33 0.1 s 0.1…600
AO12 PID2-CONT D-TIME 41.34 0.1 s 0…10
AO13 PID2-CONT D FILTER 41.35 0.1 s 0…10
AO14 COMMAND AO 1 13.91 0.1 % 0…100
AO15 COMMAND AO 2 13.92 0.1 % 0…100
AO16 EXT PID SETPOINT 71.21 0.1 % 0…100
AO17 SPD OUT MIN Derived value 0.1 % 0…200
AO18 SPD OUT MAX Derived value 0.1 % 0…200
AO19 MB PARAM N/A 1 None 0…65535
AO20 MB DATA N/A 1 None 0…65535