110 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
N2 analog output objects – Bypass
The following table lists the N2 Analog Input objects defined for the ABB E-Clipse
bypass.
N2 binary input objects – Bypass
The following table lists the N2 Binary Input objects defined for the ABB E-Clipse
bypass.
AI7 PCB TEMP 0105 0.1 °C Temperature of bypass
board
AI8 KW HOURS 0106 1 kWh Bypass-mode kilowatt hours
AI9 RUN TIME 0108 1 HR 0...65535
AI10 A-B VOLT 0111 1 V Phase A - Phase B voltage
AI11 B-C VOLT 0112 1 V Phase B - Phase C voltage
AI12 C-B VOLT 0113 1 V Phase C - Phase A voltage
N2 Analog Inputs:
Number Object
Bypass
Parameter
Resolution Units Range
AO1 BYP RUNDLY 1614 1 s 0…300
AO2 MB PARAM N/A 1 None 0…65535
AO3 MB DATA N/A 1 None 0…65535
N2 Binary Inputs:
Number Object Drive Parameter Range
BI1 SYSTEM READY Status Word 1 = Ready
BI2 SYSTEM ENABLED Status Word 1 = Enabled
BI3 SYSTEM STARTED Status Word 1 = System Started
BI4 SYSTEM RUNNING Status Word 1 = System Running
BI5 N2 LOCAL MODE Status Word 1 = N2 Local
BI6 FAULT Status Word 1 = Bypass Fault
BI7 WARNING Status Word 1 = Bypass Warning
BI8 N2 CONTROL SCR Status Word 1 = Yes
BI9 OVERRIDE Status Word 1 = Override
BI10 INPUT 1 STATUS 0103 (bit mask 1) 1 = On
BI11 INPUT 2 STATUS 0103 (bit mask 2) 1 = On
BI12 INPUT 3 STATUS 0103 (bit mask 4) 1 = On
BI13 INPUT 4 STATUS 0103 (bit mask 8) 1 = On
BI14 INPUT 5 STATUS 0103 (bit mask 10h) 1 = On
BI15 INPUT 6 STATUS 0103 (bit mask 20h) 1 = On
N2 Analog Inputs:
Number Object
Bypass
Parameter
Resolution Units Range