118 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
EFB Ref1/Ref2
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Only make these drive programming changes if you require control via BACnet.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location.
Analog output control
Using the fieldbus for analog output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the appropriate location.
Drive Parameter BACnet Access Point
19.11 Ext1/Ext2 Selection BV13
3.09 EFB Ref1 AV16
3.10 EFB Ref2 AV17
Drive Parameter Value Setting
BACnet
Access Point
10.24 RO1
Source
RELAY OUTPUT 1 62, RO/DIO control
word
Relay Output 1
controlled by fieldbus.
BO0
10.27 RELAY OUTPUT 2 62, RO/DIO control
word
Relay Output 2
controlled by fieldbus.
BO1
10.30 RELAY OUTPUT 3 62, RO/DIO control
word
Relay Output 3
controlled by fieldbus.
BO2
15.07
1)
RELAY OUTPUT 4 62, RO/DIO control
word
Relay Output 4
controlled by fieldbus.
BO3
15.10
1)
RELAY OUTPUT 5 62, RO/DIO control
word
Relay Output 5
controlled by fieldbus.
BO4
15.23
1)
DO1 Source
DIGITAL OUTPUT
1
62, RO/DIO control
word
Digital Output 1
controlled by fieldbus.
BO5
1) More than 3 relays requires the addition of a relay extension module.
Drive Parameter Value Setting
BACnet
Access
Point
13.12 AO1 Source 37, AO1 Data
Storage
Analog Output 1 controlled by
writing to parameter 13.91.
–
13.91 AO1 Data Storage – AO0
13.22 AO2 Content Sel 38, AO2 Data
Storage
Analog Output 2 controlled by
writing to parameter 13.92.
–
13.92 AO2 Data Storage – AO1