136 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
BV10 RUN/STOP CMD This Object commands a system
start. This requires bypass
parameter 1601 value = COMM
for BACnet to control.
RUN/ STOP C
BV11 OVERRIDE CMD This Object commands the
system to an override 2
condition. This requires bypass
parameter 1701 value = COMM
for BACnet to control.
YES/NO C
BV12 RUN
PERMISSIVE
CMD
This Object commands the
system Run Permissive. This
requires bypass parameter 1602
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV13 OVERRIDE ACT This Object indicates if override
1 or override 2 is active
regardless of the control source.
YES/NO R
BV14 FAULT RESET This Object resets a faulted
bypass. This requires bypass
parameter 1607 value = COMM
for BACnet to control.
RESET/ NO C
BV15 START
INTERLOCK 1
This Object commands the
system Start Interlock 1. This
requires bypass parameter 1603
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV16 START
INTERLOCK 2
This Object commands the
system Start Interlock 2. This
requires bypass parameter 1604
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV17 START
INTERLOCK 3
This Object commands the
system Start Interlock 3. This
requires bypass parameter 1605
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV18 START
INTERLOCK 4
This Object commands the
system Start Interlock 4. This
requires bypass parameter 1606
value = COMM for BACnet to
control.
ENABLE/
DISABLE
C
BV19 PAR LOCK When switched to locked
prevents parameter changes
from the panel.
LOCK /
UNLOCK
W
BV20 CTL OVERRIDE
CMD
Commands the bypass into
BACnet Control Override. In this
mode, BACnet takes the bypass
control from the normal source.
However, the panel’s HAND
mode still has priority.
ON / OFF C
BV21 MBOX READ This object reads a parameter
(defined by AV13 MBOX
PARAM) and returns it in AV14
MBOX DATA
READ /
RESET
W
Instance
ID
Object Name Description
Active/
Inactive Text
Present Value
Access Type