ACH580 E-Clipse bypass and packaged drive user manual 137
Embedded fieldbus
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays and relinquish
defaults.
BACnet analog value object instance summary – Bypass
The following table summarizes the Analog Value Objects supported:
BV22 MBOX WRITE This object writes the data value
specified by AV14, MBOX DATA,
to a parameter (defined by AV13,
MBOX PARAM).
WRITE /
RESET
W
Instance
ID
Object Name Description Units
Present Value
Access Type
AV0 CURRENT This Object indicates the measured
output current. The corresponding
bypass parameter is 0101.
Amps R
AV1 BYPASS MODE This Object indicates the Hand/Off/Auto
status of the bypass. 0=OFF; 1=HAND;
2=AUTO.
None R
AV2 BYP RUN DLY This Object sets the bypass Run delay.
The corresponding bypass parameter is
1614
Secs W
AV3 LAST FLT This Object indicates the last fault
recorded by the bypass. The
corresponding bypass parameter is 0401
None R
AV4 WARNING
WORD 1
This Object indicates the first warning
status word of the bypass. The
corresponding bypass parameter is 0308
None R
AV5 WARNING
WORD 2
This Object indicates the first warning
status word of the bypass. The
corresponding bypass parameter is 0309
None R
AV6 INPUT VOLT Average of line-line input voltage Volts R
AV7 PCB TEMP DEG C of bypass board DEG C R
AV8 KW HOURS Bypass mode kilowatt hours kWh W
AV9 RUN TIME Bypass mode run hours Hrs W
AV10 A-B VOLT Phase A - Phase B voltage Volts R
AV11 B-C VOLT Phase B - Phase C voltage Volts R
AV12 C-B VOLT Phase C - Phase A voltage Volts R
AV13 MBOX PARAM This object defines the parameter to be
read or written to by the mailbox function.
See BV21 and BV22.
None W
AV14 MBOX DATA This object holds the mailbox function’s
parameter value - a value that was read,
or is to be written. See BV21 and BV22.
None W
Instance
ID
Object Name Description
Active/
Inactive Text
Present Value
Access Type