152 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
10 REV_REF 1 Reference is in reverse direction.
0 Reference is in forward direction.
11 REV_ACT 1 System is running in reverse direction.
0 System is running in forward direction.
12 PANEL_LOCAL 1 Control is in control panel (or PC tool) local mode.
0 Control is not in control panel local mode.
13 FIELDBUS_LOCAL 1 Control is in fieldbus local mode (steals control panel local).
0 Control is not in fieldbus local mode.
14 EXT2_ACT 1 Control is in EXT2 mode.
0 Control is in EXT1 mode.
15 FAULT 1 Drive is in a fault state.
0 Drive is not in a fault state.
DCU Profile STATUS WORD
Bit Name Value Status
16 WARNING 1 An warning is on.
0 No warnings are on.
17 REQ_MAINT 1 A maintenance request is pending.
0 No maintenance request is pending.
18 DIRLOCK 1 Direction lock is ON. (Direction change is locked out.)
0 Direction lock is OFF.
19 LOCALLOCK 1 Local mode lock is ON. (Local mode is locked out.)
0 Local mode lock is OFF.
20 CTL_MODE 1 Drive is in vector control mode.
0 Drive is in scalar control mode.
21…25 Reserved
26 REQ_CTL 1 Copy the control word
0 (no op)
27 REQ_REF1 1 Reference 1 requested in this channel.
0 Reference 1 is not requested in this channel.
28 REQ_REF2 1 Reference 2 requested in this channel.
0 Reference 2 is not requested in this channel.
29 REQ_REF2EXT 1 External PID reference 2 requested in this channel.
0 External PID reference 2 is not requested in this channel.
30 ACK_STARTINH 1 A start inhibit from this channel is granted.
0 A start inhibit from this channel is not granted.
31 ACK_OFF_ILCK 1 Start inhibit due to OFF button
0 Normal operation
DCU Profile STATUS WORD
Bit Name Value Status