168 ACH580 E-Clipse bypass and packaged drive user manual
Fieldbus adapter
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Note: Relay status feedback occurs without configuration as defined below.
Drive Parameter Value Description
Protocol Reference
Modbus TCP
ABB DRV DCU PROFILE
10.24
RO1
Source
Relay Output 1
62, RO/DIO
control
word
Relay Output 1
controlled by fieldbus.
402659 bit 0 or 00033
10.27 Relay Output 2 Relay Output 2
controlled by fieldbus.
402659 bit 1 or 00034
10.30 Relay Output 3 Relay Output 3
controlled by fieldbus.
402659 bit 2 or 00035
15.07
1
Relay Output 4 Relay Output 4
controlled by fieldbus.
402659 bit 3 or 00036
15.10
1
Relay Output 5 Relay Output 5
controlled by fieldbus.
402659 bit 4 or 00037
15.23
1
DO1
Source
Digital Output 1 Digital Output 1
controlled by fieldbus.
402659 bit 8 or 00038
1) More than 3 relays requires the addition of a relay extension module.
Drive Parameter Value
Protocol Reference
Modbus TCP
ABB DRV DCU PROFILE
10.21 RO Status RO 1-3 STATUS Relay 1…3 status. 402581 or 00033...35
15.04 RO/DO Status RO 4-6 STATUS Relay 4…6 status. 403844 or 00036...37