168 ACH580 E-Clipse bypass and packaged drive user manual
Fieldbus adapter
Drive relay output control
Using the fieldbus for relay output control requires:
Drive parameter values set as defined below.
Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Note: Relay status feedback occurs without configuration as defined below.
Drive Parameter Value Description
Protocol Reference
Modbus TCP
ABB DRV DCU PROFILE
10.24
RO1
Source
Relay Output 1
62, RO/DIO
control
word
Relay Output 1
controlled by fieldbus.
402659 bit 0 or 00033
10.27 Relay Output 2 Relay Output 2
controlled by fieldbus.
402659 bit 1 or 00034
10.30 Relay Output 3 Relay Output 3
controlled by fieldbus.
402659 bit 2 or 00035
15.07
1
Relay Output 4 Relay Output 4
controlled by fieldbus.
402659 bit 3 or 00036
15.10
1
Relay Output 5 Relay Output 5
controlled by fieldbus.
402659 bit 4 or 00037
15.23
1
DO1
Source
Digital Output 1 Digital Output 1
controlled by fieldbus.
402659 bit 8 or 00038
1) More than 3 relays requires the addition of a relay extension module.
Drive Parameter Value
Protocol Reference
Modbus TCP
ABB DRV DCU PROFILE
10.21 RO Status RO 1-3 STATUS Relay 1…3 status. 402581 or 00033...35
15.04 RO/DO Status RO 4-6 STATUS Relay 4…6 status. 403844 or 00036...37