ACH580 E-Clipse bypass and packaged drive user manual 169
Fieldbus adapter
Analog output control
Using the fieldbus for analog output control (e.g. PID setpoint) requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
PID control setpoint source
Using the fieldbus for the PID control setpoint requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied setpoint value in the appropriate location.
Drive Parameter Value Description
Protocol Reference
Modbus TCP
ABB
DRV
DCU
PROFILE
13.12 AO1 Source 37, AO1 Data
Storage
Analog Output 1 controlled
by writing to parameter
13.91.
–
13.91 AO1 Data Storage – 403419
13.15 AO1 Unit Selection V or mA Voltage or current output
selection.
–
13.16 Filter AO1 – Filter time constant for
AO1
13.17
…
13.20
AO1 source min
AO1 out at AO1 src max
– Used for scaling
13.22 AO2 Source 38, AO2 Data
Storage
Analog Output 2 controlled
by writing to parameter
13.92.
–
13.92 AO2 Data Storage – 403420
13.26 AO2 Filter Time – Filter time constant for
AO2
–
13.27
…
13.30
AO2 source min
…
AO2 out at AO2 src max
– Used for scaling
Drive Parameter Value Description
Protocol
Reference
40.16 Set 1 setpoint 1
source
24 (Setpoint data
storage)
Communication channel setpoint
source
–
40.17 Set 1 setpoint 2
source
3 (AI1 scaled) Optional analog input value.
Needed if combining
communication reference with
analog input value
–
40.18 Set 1 setpoint
function
0 (In1)
1 (In1+In2)
3 (In1*In2)
Setpoint is 40.92 value itself/
+AI1/*AI1
–
40.92 Set point storage – Communication channel setpoint
value
410332
NOTE: For 41.16 – 41.18, PID set 2 can be used. Setpoint data storage still uses 40.92, even when
PID set 2 is used.