ACH580 E-Clipse bypass and packaged drive user manual 67
Parameters
Group 17: Override 2
1631 DRV/BYPASS 1 0 = KEYPAD
1 = DI5
KEYPAD
(0)
Selects source for drive/bypass
mode command.
(0) Keypad – The drive/bypass
mode selection is made
from the bypass keypad
(DRIVE or BYPASS select
keys).
(1) DI5 – The drive/bypass
mode selection from the
bypass keypad is disabled
and selection is made from
the digital input. When DI5
is energized the system is
set to bypass mode.
1640 PASS SET 0 – 65535 0 Sets the passcode that is
compared against parameter
1618- PASS CODE. Passcode
required to open.
1641 PASS CNFRM 0 – 65535 0 Confirms the setting of
parameter 1640 - PASS SET.
1642 ABB ACCESS 0 = LOCKED
1 = OPEN
LOCKED
(0)
Locks access to factory only
parameters and factory debug
tool. Passcode required to open.
1643 FB LOCK 0 = LOCKED
1 = OPEN
OPEN
(1)
Allows Fieldbus writing of
parameters. Applies to
embedded and FBA.
Does not affect control of the
bypass over the fieldbus.
Does not affect bypass
parameters in group 53- FBA
DATA OUT.
Does not affect writing of
parameters to the drive.
Passcode required to open.
1644 DNLD LOCK 0 = LOCKED
1 = OPEN
OPEN
(1)
Allows locking of program and
serial flash downloads.
Passcode required to open.
Group 17: Override 2
Code Name Resolution Range Default Description
1701 OVERRIDE 2 1 0 = NOT SEL
1 = DI5
2 = COMM
NOT SEL
(0)
Selects source for override 2
command.
1702 PERMSV OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
permissive during override 2.
1703 INTLK1 OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
interlock 1 during override 2.
1704 INTLK2 OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
interlock 2 during override 2.
1706 INTLK4 OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
interlock 4 during override 2.
1707 FAULTS OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGARD
(1)
Acknowledge or disregard
overrideable bypass faults during
override 2.
All faults can be overridden
except:
3009, 3021, 3022, 3023, 3024,
3027, 3034, 3101, 3202, 3203,
3204, 3205, 3206
1708
OVRD2 MODE
1 1 = BYPASS
2 = VFD
3 = VFD/BYPASS
4 = STOP
BYPASS
(1)
1 = Use bypass contactor only
2 = Use drive only
3 = Use drive, switch to bypass
on drive fault
4 = Both contactors open
Group 16: System Control