68 ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Note: For wiring requirements and additional configuration detail refer to Advanced
Override Mode (Override 2) on page 37.
Group 30: Fault Function
Group 32: Supervisory Control
Group 33: Information
Group 30: Fault Function
Code Name Resolution Range Default Description
3001 UL ACTION 1 0 = NOT SEL
1 = FAULT
2 = WARNING
NOT SEL
(0)
Selects action to be taken if
underload occurs.
3002 UL TIME 1 sec 10 - 400 sec 20 sec Time below underload level
before fault is declared.
3003 UL TRIP % 1% 0 - 100% 20% Sets power level at which
underload is declared.
3004 COMM LOSS 1 0 = NOT SEL
1 = FAULT
2 = CONST SP7
3 = LAST SPEED
NOT SEL
(0)
This parameter serves similar
purpose as parameter 58.14 in
drive which specifies behavior if
communication link goes down.
3005 COMM TIME 0.1s 0.0 - 600.0s 0 Sets the communication fault
time used with COMM LOSS
parameter. A value of “0”
disables the timer.
3006
PHASE LOSS
1 0 = DISABLE
1 = ENABLE
1 Provides input phase loss
detection for bypass mode.
3007 PHASE SEQ 1 0 = DISABLE
1 = ENABLE
1 Indicates if drive and bypass
would run the motor in the same
direction.
Group 32: Supervisory Control
Code Name Resolution Range Default Description
3201 SUPER CTRL 1 0 = DISABLE
1 = ENABLE
DISABLE
(0)
Enable supervisory control in
bypass mode.
3202 START LVL 1% 0 - 100% 70% Value of drive's AI2 that causes
bypass contactor closure.
Applies only in supervisory mode.
3203 STOP LEVEL 1% 0 - 100% 30% Value of drive's AI2 that causes
bypass contactor opening.
Applies only in supervisory mode.
3204 START DLY 1s 20 - 3600s 40s Time that close condition must be
present before contactor is closed.
Applies only in supervisory mode.
3205 STOP DLY 1s 20 - 3600s 60s Time that open condition must be
present before contactor is
opened.
Applies only in supervisory mode.
3206 FBK LOSS 1 0 = BYP STOP
1 = BYP START
BYP START
(1)
Bypass contactor operation if drive
link fault, drive AI2 loss or
excessive cycling.
Group 33: Information
Code Name Resolution Range Default Description
3301 FW VERSION hex Revision of main application
firmware.
3302 PT VERSION hex Revision of panel text file.
3303 LP VERSION Loading package version.
3304 CB VERSION Control board version.
3305 TEST DATE