68 ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Note: For wiring requirements and additional configuration detail refer to Advanced
Override Mode (Override 2) on page 37.
Group 30: Fault Function
Group 32: Supervisory Control
Group 33: Information
Group 30: Fault Function
Code Name Resolution Range Default Description
3001 UL ACTION 1 0 = NOT SEL
1 = FAULT
2 = WARNING
NOT SEL
(0)
Selects action to be taken if
underload occurs.
3002 UL TIME 1 sec 10 - 400 sec 20 sec Time below underload level
before fault is declared.
3003 UL TRIP % 1% 0 - 100% 20% Sets power level at which
underload is declared.
3004 COMM LOSS 1 0 = NOT SEL
1 = FAULT
2 = CONST SP7
3 = LAST SPEED
NOT SEL
(0)
This parameter serves similar
purpose as parameter 58.14 in
drive which specifies behavior if
communication link goes down.
3005 COMM TIME 0.1s 0.0 - 600.0s 0 Sets the communication fault
time used with COMM LOSS
parameter. A value of “0”
disables the timer.
3006
PHASE LOSS
1 0 = DISABLE
1 = ENABLE
1 Provides input phase loss
detection for bypass mode.
3007 PHASE SEQ 1 0 = DISABLE
1 = ENABLE
1 Indicates if drive and bypass
would run the motor in the same
direction.
Group 32: Supervisory Control
Code Name Resolution Range Default Description
3201 SUPER CTRL 1 0 = DISABLE
1 = ENABLE
DISABLE
(0)
Enable supervisory control in
bypass mode.
3202 START LVL 1% 0 - 100% 70% Value of drive's AI2 that causes
bypass contactor closure.
Applies only in supervisory mode.
3203 STOP LEVEL 1% 0 - 100% 30% Value of drive's AI2 that causes
bypass contactor opening.
Applies only in supervisory mode.
3204 START DLY 1s 20 - 3600s 40s Time that close condition must be
present before contactor is closed.
Applies only in supervisory mode.
3205 STOP DLY 1s 20 - 3600s 60s Time that open condition must be
present before contactor is
opened.
Applies only in supervisory mode.
3206 FBK LOSS 1 0 = BYP STOP
1 = BYP START
BYP START
(1)
Bypass contactor operation if drive
link fault, drive AI2 loss or
excessive cycling.
Group 33: Information
Code Name Resolution Range Default Description
3301 FW VERSION hex — Revision of main application
firmware.
3302 PT VERSION hex — Revision of panel text file.
3303 LP VERSION — — Loading package version.
3304 CB VERSION — — Control board version.
3305 TEST DATE — —