ACH580 E-Clipse bypass and packaged drive user manual 69
Parameters
Group 50: Bypass EFB
3306 DRIVE TYPE Drive Type - copy of drive's
parameter 07.03.
3307 SUB ASMBLY Bypass Sub assembly type.
3308 PLANT CODE 1 0-9 0 Part of bypass serial number:
Shows 1 digit plant code. Identifies
the factory where the device was
made
3309 MFG
DATE
1 0107 - 5299 0 Part of bypass serial number:
Shows 4 digit manufacturing date.
WWYY. (2 digits for the week
number 01-52 and 2 digits for the
year)
3310 UNIT
NUM
1 00001 - 65535 0 Part of bypass serial number:
Shows 5 digit unit number here.
Tells order number of a unit
manufactured during a certain
week. Maximum number is 65525.
Group 50: Bypass EFB
Code Name Resolution Range Default Description
5003 BP MAC ID 1 0 - 65535 256 Bypass station ID (NODE ADDRESS)
5008 BP OK MSG 1 0 - 65535 0 Contains a count of valid messages received by the
bypass.
During normal operation, this counter is increasing
constantly.
5013 TOKEN CNT 1 0 - 65535 0 Contains a count of the number of times the bypass
has received the token.
5040 BP OB ID L 1 0 - 65535 0 BACnet Device object ID lower word.
The Bypass’s Device object ID must be unique
across all BACnet devices in the building network.
Valid values are 0…4194303. The Device Object ID
is formed as a combination of parameter 5040 and
5099. To set an ID from 1 to 65535 set this
parameter = to the desired ID and set 5099 = 0. To
set an ID greater than 65535, set this parameter to
the lower 4 digits of the ID and set 5099 to the
remaining upper digits. For example, to set the ID to
71234, set the 5040 = 1234 and 5099 = 7. The
default values of 5040 = 0 and 5099 = 0 are
handled specially. This case uses parameter 5003,
the MAC ID as the value for the device object ID.
5099 BP OB ID H 1 0 - 419 0 BACnet Device object ID upper word. See
parameter 5040 for description of how to use this
parameter.
Group 33: Information
Code Name Resolution Range Default Description