ACH580 E-Clipse bypass and packaged drive user manual 71
Parameters
Group 53: FBA Data Out
Group 58: Drive EFB
The drive's Group 58 must be replicated on bypass, since the EFB link on the drive
is reserved for internal communication with the bypass. All Group 58 functionality
associated with selection by 98.02 is hosted on the bypass controller for drive.
Group 58 parameters on the bypass are a subset of the Group 58 parameters on the
drive.
Group 53: FBA Data Out
Code Name Resolution Range Default Description
5301
...
5310
DATA OUT 1
...
DATA OUT10
1 0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1 (ABBDP)
6 = Actual Value 2 (ABBDP)
0101h -063FFh = Drive
parameters
8101h - E3FFh = Bypass
parameters + 8000h
— Specifies information to be
written to the drive (out of
the network). Only for
modules that support the
cyclic low scanner function
(such as FMBT-12).
For specifying values 1-6,
select ABB drive’s profile
information, like control
word of reference.
To specify drive
parameters, use the format
ggh.pph where gg
h
is the
parameter group in
hexadecimal and pp
h
is the
parameter in hexadecimal.
For instance, drive
parameter 30.14 is
encoded as 1E0Eh.
Bypass parameter is
specified as 8000h +
gg
h
.pp
h
. For instance,
bypass parameter 0114 is
encoded as 810Eh.
Group 58: Drive EFB
Code Name Resolution Range Default Description
5802 DV PROT ID hex 0x0000 - 0xFFFF 0x0000 Protocol ID and revision:
Format:
XXYY where XX = protocolID and
YY = program revision
5803 DV MAC ID 1 0 - 65535 256 Default value is protocol-
dependent: Modbus and N2 is 1,
BACnet is 128. Drive station ID
(NODE ADDRESS)
Refer to Communication setup –
EFB on page 79 for more
information.
5804 BAUD RATE 0.1 kbit/s 1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6, 76.8
9.6 Default value is protocol-
dependent: Modbus and N2 is
9.6, BACnet is 38.4. Defines the
communication speed of the
RS485 link in kbits per second
(kb/s).
Refer to Communication setup –
EFB on page 79 for more
information.
5805 EFB PARITY 1 0=8 NONE 1,
1=8 NONE 2,
2=8 EVEN 1,
3=8 ODD 1
0 Defines the data length, parity and
stop bits to be used with the
RS485 link communication.
Default value is protocol-
dependent: Modbus is 1, N2 and
BACnet is 0. Refer to
Communication setup – EFB on
page 79 for more information.