72 ACH580 E-Clipse bypass and packaged drive user manual
Parameters
5807 DV STATUS 1 0=IDLE,
1=EXECUT INIT,
2=TIME OUT,
3=CONFIG ERR,
4=OFF-LINE,
5=ON-LINE,
6=RESET,
7=LISTEN ONLY
0 Contains the status of the drive
EFB protocol.
5808 DV OK MSG 1 0 - 65535 0 Contains a count of valid
messages received by the drive.
During normal operation, this
counter is increasing
constantly.
5811 UART ERROR 1 0 - 65535 0 Contains a count of the messages
with a character error received by
the drive.
5812 DV CRC ERR 1 0 - 65535 0 Contains a count of the messages
with a CRC error received by the
drive.
5813 TOKEN CNT 1 0 - 65535 0 Contains a count of the number of
times the drive has received the
token.
5817 TX DELAY 1 0 - 65535 0 Defines the drive minimum
response delay in addition to any
fixed delay imposed by the
protocol.
5818 EFB CNTRL 1 0 - 0xFFFF 0 Displays the raw (unmodified)
control word sent by the Modbus
controller to the drive. This
parameter is read-only.
5819 EFB STAT 1 0 - 0xFFFF 0 Status word sent by the drive to
the Modbus controller. this
parameter is read-only.
5825 PROFILE 1 0=ABB DRV LIM,
1=DCU PROFILE,
2=ABB DRV FULL
0 Selects the communications
profile used by the EFB protocol.
5840 DV OB ID L 1 0 - 65535 4303 BACnet Device object ID lower
word.
The Drive’s Device object ID must
be unique across all BACnet
devices in the building network.
Valid values are 0…4194303. The
Device Object ID is formed as a
combination of parameter 5840
and 5899. To set an ID from 1 to
65535 set this parameter = to the
desired ID and set 5899 = 0. To
set an ID greater than 65535, set
this parameter to the lower 4 digits
of the ID and set 5899 to the
remaining upper digits. For
example, to set the ID to 71234,
set the 5840 = 1234 and 5899 = 7.
The default values of 5840 = 0
and 5899 = 0 are handled
specially. This case uses
parameter 5803, the MAC ID as
the value for the device object ID.
5841 MAX MASTER 1 0 - 127 127 The Drive’s highest master
address for devices on the
BACnet MS/TP bus.
5842 MAX INF FR 1 0 - 10 1 The maximum number of
information frames the drive may
transmit before it must pass the
token.
5899 DV OB ID H 1 0 - 419 419 BACnet Device object ID upper
word. See parameter 58.40 for
description of how to use this
parameter.
58100 DB REV 1 0 - 65535 0 BACnet Database Revision