ABB Chapter 4 - Changing 3/5 MVA Phase Modules
ACS 6000 Maintenance Manual 3BHS202077 ZAB E01 Rev. C 4-7 (10)
14 Lift the phase module high enough to be able to withdraw the rails.
Figure 4-10 Phase Module Attached to Hoist
15 After the rails have been removed slowly lower the phase module to
the floor.
Using a Crane
16 Screw the two eyebolts into the tapped holes of the lifting bar, attach
the phase module to the crane and lift it from the rails.
Figure 4-11 Phase Module Attached to Crane
Fastening bolts