119 ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV. J
8.1 Operating conditions
The operating conditions for the drive are according to IEC 60721-3-3
’Stationary use at weather-protected locations’ (deviations from the
standard are indicated).
Table 8-1 Operating conditions
If the operating conditions are not within the spec-
ifications, contact ABB.
3K3 Climatic conditions
Air temperature 5 – 40 °C
Relative humidity 5 – 85%
Absolute humidity
1 – 25 g/m
3
Condensation No
3B1 Biological conditions
Flora No
Fauna No
3C2 Chemically active substances
Sea salt and road salts Salt mist
Mean value Max. value
Sulphur dioxide
0.3 mg/m
3
1.0 mg/m
3
Hydrogen sulfide
0.1 mg/m
3
0.5 mg/m
3
Chlorine
0.1 mg/m
3
0.3 mg/m
3
Hydrogen chloride
0.1 mg/m
3
0.5 mg/m
3
Hydrogen fluoride
0.01 mg/m
3
0.03 mg/m
3
Ammonia
1 mg/m
3
3 mg/m
3
Ozone
0.05 mg/m
3
0.1 mg/m
3
Nitrogen oxides
0.5 mg/m
3
1.0 mg/m
3
3S2 Mechanically active substances
Sand
30 mg/m
3
Dust (suspension)
0.2 mg/m
3
Dust (sedimentation)
1.5 mg/m
3
3M3 Mechanical conditions
Stationary vibration sinusoidal
Displacement amplitude 1.5 mm (2 – 9 Hz)
Acceleration amplitude
5 m/s
2
(9 – 200 Hz)
Non-stationary vibration (including shock)
Shock response spectrum
70 m/s
2
For the maximum ambient temperature,
see the rating label of the drive.