WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment.
The drive is not field repairable. Never attempt to repair a malfunctioning drive; contact your local ABB representative or
Authorized Service Centre for replacement.
Make sure that dust from drilling does not enter the drive during the installation. Electrically conductive dust inside the drive may
cause damage or lead to malfunction.
Ensure sufficient cooling.
Safety in start-up and operation
These warnings are intended for all who plan the operation, start up or operate the drive.
WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment.
Before adjusting the drive and putting it into service, make sure that the motor and all driven equipment are suitable for
operation throughout the speed range provided by the drive. The drive can be adjusted to operate the motor at speeds
above and below the speed provided by connecting the motor directly to the power line.
Do not activate automatic fault reset functions if dangerous situations can occur. When activated, these functions reset the
drive and resume operation after a fault.
Do not control the motor with an AC contactor or disconnecting device (disconnecting means); use instead the control panel
start and stop keys and or external commands (I/O). The maximum allowed number of charging cycles of the DC capacitors
(that is, power-ups by applying power) is two per minute.
Note:
When parameter 1103 PRIMARY COMMAND SOURCE MODE is not set to 1 or 2, the stop key on the control panel will not
stop the drive. To stop the drive open terminal 2 of the drive control terminals.